Saci (AHM1) - MODBUS Registers
Registers in the map: 354 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, single, smallint.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 6 | V1 | V | single | |
| 8 | V2 | V | single | |
| 10 | V3 | V | single | |
| 12 | V12 | V | single | |
| 14 | V23 | V | single | |
| 16 | V31 | V | single | |
| 18 | I1 | A | single | |
| 20 | I2 | A | single | |
| 22 | I3 | A | single | |
| 24 | In (3P4W) | A | single | |
| 26 | P1 | kW | single | |
| 28 | P2 | kW | single | |
| 30 | P3 | kW | single | |
| 32 | P | kW | single | |
| 34 | Q1 | kvar | single | |
| 36 | Q2 | kvar | single | |
| 38 | Q3 | kvar | single | |
| 40 | Q | kvar | single | |
| 42 | S1 | kVA | single | |
| 44 | S2 | kVA | single | |
| 46 | S3 | kVA | single | |
| 48 | S | kVA | single | |
| 50 | PF1 | | single | |
| 52 | PF2 | | single | |
| 54 | PF3 | | single | |
| 56 | PF | | single | |
| 58 | F | Hz | single | |
| 60 | Average value of vph-N | V | single | |
| 62 | Average value of vph-ph | V | single | |
| 64 | Average current | A | single | |
| 66 | Import active energy | kWh | single | |
| 68 | Export active energy | kWh | single | |
| 70 | Import reactive energy | kvarh | single | |
| 72 | Export reactive energy | kvarh | single | |
| 74 | Apparent energy | kVAh | single | |
| 76 | Q1 reactive energy - EQL+ | kvarh | single | |
| 78 | Q2 reactive energy - EQC+ | kvarh | single | |
| 80 | Q3 reactive energy - EQL- | kvarh | single | |
| 82 | Q4 reactive energy - EQC- | kvarh | single | |
| 84 | Hour meter - EP+ | s | single | |
| 86 | Hour meter - EP- | s | single | |
| 88 | Alternative import active energy | kWh | single | |
| 90 | Alternative export active energy | kWh | single | |
| 92 | Alternative import reactive energy | kvarh | single | |
| 94 | Alternative export reactive energy | kvarh | single | |
| 96 | Alternative apparent energy | kVAh | single | |
| 98 | Alternative energy - EQL+ | kvarh | single | |
| 100 | Alternative energy - EQC+ | kvarh | single | |
| 102 | Alternative energy - EQL- | kvarh | single | |
| 104 | Alternative energy - EQC- | kvarh | single | |
This is not the complete map: 50 of 354 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Saci (ANG96) - MODBUS Registers Map
Registers in the map: 89 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: dword, single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Voltage | V | single | |
| 2 | Voltage | V | single | |
| 4 | Current L1 | A | single | |
| 6 | THD% current L1 | % | single | |
| 8 | THD% voltage | % | single | |
| 16 | Active power L1 | kW | single | |
| 18 | Power factor | | single | |
| 20 | Reactive power L1 | kvar | single | |
| 22 | Apparent power L1 | kVA | single | |
| 24 | Voltage | V | single | |
| 32 | Voltage | V | single | |
| 34 | Current L2 | A | single | |
| 36 | THD% current L2 | % | single | |
| 38 | THD% voltage | % | single | |
| 40 | Active power L2 | kW | single | |
| 48 | Power factor | | single | |
| 50 | Reactive power L2 | kvar | single | |
| 52 | Apparent power L2 | kVA | single | |
| 54 | Voltage | V | single | |
| 56 | Voltage | V | single | |
| 64 | Current L3 | A | single | |
| 66 | THD% current L3 | % | single | |
| 68 | THD% voltage | % | single | |
| 70 | Active power L3 | kW | single | |
| 72 | Power factor | | single | |
| 80 | Reactive power L3 | kvar | single | |
| 82 | Apparent power L3 | kVA | single | |
| 84 | Neutral current | A | single | |
| 86 | Frequency | Hz | single | |
| 88 | Power factor | | single | |
| 96 | Apparent power total | kVA | single | |
| 98 | Active power total | kW | single | |
| 100 | Reactive power total | kvar | single | |
| 102 | Import active energy | kWh | single | |
| 104 | Export active energy | kWh | single | |
| 112 | Reactive energy. inductive | kvarh | single | |
| 114 | Reactive energy. capacitive | kvarh | single | |
| 116 | Generator mode. import active energy | kWh | single | |
| 118 | Generator mode. export active energy | kWh | single | |
| 120 | Generator mode. reactive energy. inductive | kvarh | single | |
| 128 | Generator mode. reactive energy. capacitive | kvarh | single | |
| 130 | Import active energy time counter | | dword | |
| 132 | Export active energy time counter | | dword | |
| 134 | Generator mode. import active energy time counter | | dword | |
| 136 | Generator model. export active energy time counter | | dword | |
| 256 | Current L1 | A | single | |
| 258 | Current L1 | A | single | |
| 260 | Current L2 | A | single | |
| 262 | Current L2 | A | single | |
| 264 | Current L3 | A | single | |
This is not the complete map: 50 of 89 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Saci (M2DL2) - MODBUS Measurements
Connection and addressing notes
- Protocol
- Modbus
- Read function codes
- 0x03 and 0x04 (input and holding registers)
- Write function code
- 0x10 multiple registers
- Register 0021
- high byte = Modbus ID, low byte = baud rate code
- Baud rate code
- 1 = 9600, 2 = 4800, 3 = 2400, 4 = 1200 bps
- Device address and baud rate
- read and written together
Registers in the map: 15. function 4 (input registers). byte order big-endian. data types: dword, word.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 0 | Global active energy accumulator | kWh | dword | ×0.1 |
| 8 | Export active energy accumulator | kWh | dword | ×0.1 |
| 10 | Import active energy accumulator | kWh | dword | ×0.1 |
| 12 | Voltage | V | word | ×0.1 |
| 13 | Current | A | word | ×0.1 |
| 14 | Active power | W | word | |
| 15 | Reactive power | W | word | |
| 16 | Power factor | | word | ×0.001 |
| 17 | Frequency | Hz | word | ×0.1 |
| 256 | Import reactive energy accumulator Q1 + Q2 | kWh | dword | ×0.1 |
| 258 | Export reactive energy accumulator Q3 + Q4 | kWh | dword | ×0.1 |
| 260 | Q1 reactive energy accumulator | kWh | dword | ×0.1 |
| 262 | Q2 reactive energy accumulator | kWh | dword | ×0.1 |
| 264 | Q3 reactive energy accumulator | kWh | dword | ×0.1 |
| 266 | Q4 reactive energy accumulator | kWh | dword | ×0.1 |
Saci (TCIL2) - MODBUS Measurements
Connection and addressing notes
- Device address register
- 2054 high byte, range 1-247
- Baud rate register
- 2054 low byte, 0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600, 4 = 19200 bps
Registers in the map: 374 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single, smallint.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 86 | Total power factor | | single | |
| 88 | Grid frequency | Hz | single | |
| 96 | Average value of three phase voltages | V | single | |
| 98 | Average value of three line voltages | V | single | |
| 100 | Average value of three phase currents | A | single | |
| 102 | EP+ | kWh | single | |
| 104 | EP- | kWh | single | |
| 112 | EQ+ | kvarh | single | |
| 114 | EQ- | kvarh | single | |
| 116 | Apparent energy | kVAh | single | |
| 118 | Trip energy | kWh | single | |
| 120 | First-quadrant reactive energy EQL+ | kvarh | single | |
| 128 | Second-quadrant reactive energy EQC+ | kvarh | single | |
| 130 | Third-quadrant reactive energy EQL- | kvarh | single | |
| 132 | Four-quadrant reactive energy EQC- | kvarh | single | |
| 134 | Import active energy[total | kWh | single | |
| 136 | Import active energy[tip | kWh | single | |
| 144 | Import active energy[peak | kWh | single | |
| 146 | Import active energy[flat | kWh | single | |
| 148 | Import active energy[valley | kWh | single | |
| 150 | Export active energy[total | kWh | single | |
| 152 | Export active energy[tip | kWh | single | |
| 256 | Export active energy[peak | kWh | single | |
| 258 | Export active energy[flat | kWh | single | |
| 260 | Export active energy[valley | kWh | single | |
| 262 | Import active energy of this month[total | kWh | single | |
| 264 | Import active energy of this month[tip | kWh | single | |
| 272 | Import active energy of this month[peak | kWh | single | |
| 274 | Import active energy of this month[flat | kWh | single | |
| 276 | Import active energy of this month[valley | kWh | single | |
| 278 | Export active energy of this month[total | kWh | single | |
| 280 | Export active energy of this month[tip | kWh | single | |
| 288 | Export active energy of this month[peak | kWh | single | |
| 290 | Export active energy of this month[flat | kWh | single | |
| 292 | Export active energy of this month[valley | kWh | single | |
| 294 | Import active energy of last month[total | kWh | single | |
| 296 | Import active energy of last month[tip | kWh | single | |
| 304 | Import active energy of last month[peak | kWh | single | |
| 306 | Import active energy of last month[flat | kWh | single | |
| 308 | Import active energy of last month[valley | kWh | single | |
| 310 | Export active energy of last month[total | kWh | single | |
| 312 | Export active energy of last month[tip | kWh | single | |
| 320 | Export active energy of last month[peak | kWh | single | |
| 322 | Export active energy of last month[flat | kWh | single | |
| 324 | Export active energy of last month[valley | kWh | single | |
| 326 | Import active energy two month before[total | kWh | single | |
| 328 | Import active energy two month before[tip | kWh | single | |
| 336 | Import active energy two month before[peak | kWh | single | |
| 338 | Import active energy two month before[flat | kWh | single | |
| 340 | Import active energy two month before[valley | kWh | single | |
This is not the complete map: 50 of 374 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.