Schneider Electric (EM3502,EM3550) data logging - MODBUS registers map


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offset
Description
Units
Data type
2
Total instantaneous real power (3 phase total)
kW
word
3
Total instantaneous reactive power (3 phase total)
kVAR
word
4
Total instantaneous apparent power (3 phase total)
kVA
word
5
Total power factor (total kw / total kva)
Ratio
word
6
Voltage, L l, average of 3 phases
Volt
word
7
Voltage, L n, average of 3 phases
Volt
word
8
Current, average of 3 phases
Amp
word
9
Real power, phase A
kW
word
10
Real power, phase B
kW
word
11
Real power, phase C
kW
word
12
Power factor, phase A
Ratio
word
13
Power factor, phase B
Ratio
word
14
Power factor, phase C
Ratio
word
15
Voltage, phase A B
Volt
word
16
Voltage, phase B C
Volt
word
17
Voltage, phase A C
Volt
word
18
Voltage, phase A N
Volt
word
19
Voltage, phase B N
Volt
word
20
Voltage, phase C N
Volt
word
21
Current, instantaneous, phase A
Amp
word
22
Current, instantaneous, phase B
Amp
word
23
Current, instantaneous, phase C
Amp
word
25
Frequency (derived from phase a)
Hz
word
26
Apparent energy consumption (msr)
KVAh
dword
28
Reactive energy consumption (msr)
KVARh
dword
30
Apparent power, phase A
kVA
word
31
Apparent power, phase B
kVA
word
32
Apparent power, phase C
kVA
word
33
Reactive power, phase A
kVAR
word
34
Reactive power, phase B
kVAR
word
35
Reactive power, phase C
kVAR
word
36
Total real power present demand
kW
word
37
Total reactive power present demand
kVAR
word
38
Total apparent power present demand
kVA
word
39
Total real power max. demand
kW
word
40
Total reactive power max. demand
kVAR
word
41
Total apparent power max. demand
kVA
word
42
Pulse counter 1 (real energy)
 
dword
44
Pulse counter 2 (reactive energy)
 
dword
46
Real energy consumption phase A
kWh
dword
48
Real energy consumption phase B
kWh
dword
50
Real energy consumption phase C
kWh
dword
129
Single phase: A + N
 
word
130
Ct ratio primary
Amps
word
131
Ct ratio secondary interface (1 or 1/3 v, may not be user configurable)
 
word
132
Pt ratio: the meter scales this value by 100 (i.e. entering 200 yields a potential transformer ratio of 2:1). the default is 100 (1.00:1), which is with no pt attached. set this value before setting the system voltage (below)
 
word
133
System voltage: this voltage is line to line, except for system type 10 which is line to neutral. the meter uses this value to calculate the full scale power for the analog outputs and pulse configuration (below), and as full scale for phase loss (register 142). the meter will refuse voltages that are outside the range of 82 660 volts when divided by the pt ratio (above)
 
word
134
Theoretical maximum system power: this read only value is the theoretical maximum power the meter can expect to see on a service. this value is 100% of scale on the analog output (0 5 vdc or 4 20 ma), if equipped. the meter recalculates this value if the user changes the ct size, system type, or system voltage. this integer value has the same scale as other integer power registers (see register 140 for power scaling)
kW
word
136
Display units: 0 = iec (u, v, p, q, s), 1 = ieee (default: vll, vln, w, var, va)
 
word
137
Scale factors note: these registers contain a signed integer that scales the corresponding integer registers. floating point registers are not scaled. scaling is recalculated when the meter configuration is changed
 
smallint
There are more MODBUS items for this device. Please download the program to discover all registers.

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.