Schneider Electric PM9C logging. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
100 | Current transformer ratio (ct) | | word |
101 | Voltage transformer ratio (pt) | | word |
102 | System type | | word |
103 | Type of power demand: (dmd type) | | word |
104 | Demand calculation interval (dmd time) | minute | word |
200 | Reset of | | word |
1000 | I1: phase 1 current | mA | dword |
1002 | I2: phase 2 current | mA | dword |
1004 | I3: phase 3 current | mA | dword |
1006 | In: neutral current | mA | dword |
1008 | U12: line 1 to line 2 voltage | mV | dword |
1010 | U23: line 2 to line 3 voltage | mV | dword |
1012 | U31: line 3 to line 1 voltage | mV | dword |
1014 | V1n: line 1 to neutral voltage | mV | dword |
1016 | V2n: line 2 to neutral voltage | mV | dword |
1018 | V3n: line 3 to neutral voltage | mV | dword |
1020 | F: frequency | Hz | dword |
1022 | P: total active power (+/- signed value) | kW | dword |
1024 | Q: total reactive power (+/- signed value) | kvar | dword |
1026 | S: total apparent power | kVA | dword |
1028 | Pf: total power factor (+/- signed value) | | dword |
1030 | Power factor sector | | dword |
1032 | Power demand: active or reactive or apparent (see reg. 104) | kW | dword |
1034 | Max power demand: active or reactive or apparent (see reg. 104) | kW | dword |
1036 | Operating time counter | | dword |
1038 | Active energy total counter | kWh | dword |
1040 | Reactive energy total counter | kvarh | dword |
1042 | Active energy partial counter | kWh | dword |
1044 | P1: phase 1 active power (+/- signed value) | kW | dword |
1046 | P2: phase 2 active power (+/- signed value) | kW | dword |
1048 | P3: phase 3 active power (+/- signed value) | kW | dword |
1050 | Q1: phase 1 reactive power (+/- signed value) | kvar | dword |
1052 | Q2: phase 2 reactive power (+/- signed value) | kvar | dword |
1054 | Q3: phase 3 reactive power (+/- signed value) | kvar | dword |
Schneider Electric (CM2000) data logging
Schneider Electric (EM1000,EM1100,EM1200) data logging
Schneider Electric (EM3502,EM3550) data logging
Schneider Electric (EM4200) data logging
Schneider Electric (EM6400) data logging
Schneider Electric (EM6400NG,PM2100,PM2200) data logging
Schneider Electric (EM7200) data logging
Schneider Electric (EMB,EME) data logging
Schneider Electric (iEM3000) data logging
Schneider Electric (PM600) data logging
Schneider Electric (PM8000) data logging
Schneider Electric (PVSCL20E) data logging
Schneider Electric (Sepam 40) data logging
Schneider Electric (Sepam 60) data logging
Schneider Electric (Sepam 80) data logging
Schneider Electric (Symmetra PX) data logging
Schneider Electric PM1000 PM1200 data logging
Schneider Electric PM9C data logging
Schneider Electric PowerLogic ION6200 data logging
Schneider Electric PowerLogic ION7300 data logging
Schneider Electric PowerLogic ION7500-ION7600 data logging
Schneider Electric PowerLogic ION7550-ION7650 data logging
Schneider Electric PowerLogic ION8300-ION8400-ION8500 data logging
Schneider Electric PowerLogic ION8600 data logging
Schneider Electric PowerLogic ION8800 data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.