Seneca S203, S604, S700, Z203 MODBUS registers: read online

Connect Seneca to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Seneca logger and poll.

Do you not know the meter address? Scan the device address online

Seneca (S203) - MODBUS Mapping

Connection and addressing notes

Register addressing
registers are 4xxxx holding register numbers and the map uses 0-based offsets (40135 = 134)
32-bit floats
occupy two registers with the MSW at the lower address and the LSW at the next one
Normalized values
16 bit words (0 to 10000)
Configuration
Easy-SETUP configuration is possible over RS232 or RS485

Registers in the map: 53 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single, word.

MODBUS offsetDescriptionUnitsData typeScale
134Voltage A single 
136Voltage B single 
138Voltage C single 
140Voltage 3ph single 
192Voltage A word 
193Voltage B word 
194Voltage C word 
195Voltage 3ph word 
142Current A single 
144Current B single 
146Current C single 
148Current 3ph single 
196Current A word 
197Current B word 
198Current C word 
199Current 3ph word 
150Active pow A single 
152Active pow B single 
154Active pow C single 
156Active pow 3ph single 
200Active pow A word 
201Active pow B word 
202Active pow C word 
203Active pow 3ph word 
158Reactive pow A single 
160Reactive pow B single 
162Reactive pow C single 
164Reactive pow 3 ph single 
204Reactive pow A word 
205Reactive pow B word 
206Reactive pow C word 
207Reactive pow 3 ph word 
166Apparent pow A single 
168Apparent pow B single 
170Apparent pow C single 
172Apparent pow 3 ph single 
208Apparent pow A word 
209Apparent pow B word 
210Apparent pow C word 
211Apparent pow 3 ph word 
184Energy A single 
186Energy B single 
188Energy C single 
190Energy 3ph single 
174Cos A single 
176Cos B single 
178Cos C single 
180Cos 3ph single 
212Cos A word 
213Cos B word 

This is not the complete map: 50 of 53 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Seneca (S604) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Function codes
03 and 04 read the registers
Register addressing
addresses are hexadecimal and used directly as 0-based offsets
Value size
each value occupies 2 words
INTEGER register bank
starts at 0x0000
IEEE register bank
starts at 0x1000 in the same register bank

Registers in the map: 397 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
4096Phase 1 N voltageVsingle 
4098Phase 2 N voltageVsingle 
4100Phase 3 N voltageVsingle 
4102Line 12 voltageVsingle 
4104Line 23 voltageVsingle 
4106Line 31 voltageVsingle 
4108System voltageVsingle 
4110Phase 1 currentAsingle 
4112Phase 2 currentAsingle 
4114Phase 3 currentAsingle 
4116Neutral currentAsingle 
4118System currentAsingle 
4120Phase 1 active powerWsingle 
4122Phase 2 active powerWsingle 
4124Phase 3 active powerWsingle 
4126System active powerWsingle 
4128Phase 1 apparent powerVAsingle 
4130Phase 2 apparent powerVAsingle 
4132Phase 3 apparent powerVAsingle 
4134System apparent powerVAsingle 
4136Phase 1 reactive powervarsingle 
4138Phase 2 reactive powervarsingle 
4140Phase 3 reactive powervarsingle 
4142System reactive powervarsingle 
4144Phase 1 power factor single 
4146Phase 2 power factor single 
4148Phase 3 power factor single 
4150System power factor single 
4152Phase 1 dpf single 
4154Phase 2 dpf single 
4156Phase 3 dpf single 
4158Phase 1 tangent single 
4160Phase 2 tangent single 
4162Phase 3 tangent single 
4164System tangent single 
4166Phase 1 N voltage thd%single 
4168Phase 2 N voltage thd%single 
4170Phase 3 N voltage thd%single 
4172Line 12 voltage thd%single 
4174Line 23 voltage thd%single 
4176Line 31 voltage thd%single 
4178Phase 1 current thd%single 
4180Phase 2 current thd%single 
4182Phase 3 current thd%single 
4184Neutral current thd%single 
4186FrequencyHzsingle 
4188Sequence ($00=123 ccw, $01=321 cw, $02=not defined) single 
4190Hourcounterhsingle 
4192Hourcounterhsingle 
4366Phase 1 current dmdAsingle 

This is not the complete map: 50 of 397 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Seneca (S700) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Function codes
03 and 04 read the registers
Register addressing
addresses are hexadecimal and used directly as 0-based offsets
Value size
each value occupies 2 words
INTEGER register bank
starts at 0x0000
IEEE register bank
starts at 0x1000 in the same register bank

Registers in the map: 397 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
4096Phase 1 N voltageVsingle 
4098Phase 2 N voltageVsingle 
4100Phase 3 N voltageVsingle 
4102Line 12 voltageVsingle 
4104Line 23 voltageVsingle 
4106Line 31 voltageVsingle 
4108System voltageVsingle 
4110Phase 1 currentAsingle 
4112Phase 2 currentAsingle 
4114Phase 3 currentAsingle 
4116Neutral currentAsingle 
4118System currentAsingle 
4120Phase 1 active powerWsingle 
4122Phase 2 active powerWsingle 
4124Phase 3 active powerWsingle 
4126System active powerWsingle 
4128Phase 1 apparent powerVAsingle 
4130Phase 2 apparent powerVAsingle 
4132Phase 3 apparent powerVAsingle 
4134System apparent powerVAsingle 
4136Phase 1 reactive powervarsingle 
4138Phase 2 reactive powervarsingle 
4140Phase 3 reactive powervarsingle 
4142System reactive powervarsingle 
4144Phase 1 power factor single 
4146Phase 2 power factor single 
4148Phase 3 power factor single 
4150System power factor single 
4152Phase 1 dpf single 
4154Phase 2 dpf single 
4156Phase 3 dpf single 
4158Phase 1 tangent single 
4160Phase 2 tangent single 
4162Phase 3 tangent single 
4164System tangent single 
4166Phase 1 N voltage thd%single 
4168Phase 2 N voltage thd%single 
4170Phase 3 N voltage thd%single 
4172Line 12 voltage thd%single 
4174Line 23 voltage thd%single 
4176Line 31 voltage thd%single 
4178Phase 1 current thd%single 
4180Phase 2 current thd%single 
4182Phase 3 current thd%single 
4184Neutral current thd%single 
4186FrequencyHzsingle 
4188Sequence ($00=123 ccw, $01=321 cw, $02=not defined) single 
4190Hourcounterhsingle 
4192Hourcounterhsingle 
4366Phase 1 current dmdAsingle 

This is not the complete map: 50 of 397 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Seneca (Z203) - MODBUS Maps

Connection and addressing notes

Register addressing
registers are 4xxxx holding register numbers and the map uses 0-based offsets (40081 = 80)
32-bit floats
occupy two registers with the MSW at the lower address and the LSW at the next one
Energy value
signed long in two registers

Registers in the map: 11. function 3 (holding registers). byte order big-endian. data types: single, word.

MODBUS offsetDescriptionUnitsData typeScale
80Voltage single 
94Voltage word 
82Current single 
95Current word 
84Active power single 
88Reactive power single 
97Reactive power single 
90Cos single 
98Cos single 
86Freq single 
100Frequency word 