Siemens SEM3 Dual Phase MODBUS registers: read online

Connect Siemens to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Siemens logging and read.

Do you not know the meter address? Scan the device address online

Siemens (SEM3 Dual Phase) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Register addressing
the Modbus Address External column gives 4xxxx register numbers (0-based offset = number minus 40001)
Alarm flag registers
one register, bit field, read write
Alarm bit clearing
write 1 to an alarm bit to clear it
Monitor data block addressing
addressed as Base plus offset
Monitor data types
Float 32, uint 16, uint 32 or uint 64
Registers per monitor value
2 or 4

Registers in the map: 2708 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
100Monitor 1 alarm flags word 
101Monitor 2 alarm flags word 
102Monitor 3 alarm flags word 
103Monitor 4 alarm flags word 
104Monitor 5 alarm flags word 
105Monitor 6 alarm flags word 
106Monitor 7 alarm flags word 
107Monitor 8 alarm flags word 
108Monitor 9 alarm flags word 
109Monitor 10 alarm flags word 
110Monitor 11 alarm flags word 
111Monitor 12 alarm flags word 
112Monitor 13 alarm flags word 
113Monitor 14 alarm flags word 
114Monitor 15 alarm flags word 
115Monitor 16 alarm flags word 
116Monitor 17 alarm flags word 
117Monitor 18 alarm flags word 
118Monitor 19 alarm flags word 
119Monitor 20 alarm flags word 
120Monitor 21 alarm flags word 
121Monitor 22 alarm flags word 
122Monitor 23 alarm flags word 
123Monitor 24 alarm flags word 
124Monitor 25 alarm flags word 
125Monitor 26 alarm flags word 
126Monitor 27 alarm flags word 
127Monitor 28 alarm flags word 
128Monitor 29 alarm flags word 
129Monitor 30 alarm flags word 
130Monitor 31 alarm flags word 
131Monitor 32 alarm flags word 
132Monitor 33 alarm flags word 
133Monitor 34 alarm flags word 
134Monitor 35 alarm flags word 
135Monitor 36 alarm flags word 
136Monitor 37 alarm flags word 
137Monitor 38 alarm flags word 
138Monitor 39 alarm flags word 
139Monitor 40 alarm flags word 
140Monitor 41 alarm flags word 
141Monitor 42 alarm flags word 
142Monitor 43 alarm flags word 
143Monitor 44 alarm flags word 
144Monitor 45 alarm flags word 
145Monitor 46 alarm flags word 
146Monitor 47 alarm flags word 
147Monitor 48 alarm flags word 
148Monitor 49 alarm flags word 
149Monitor 50 alarm flags word 

This is not the complete map: 50 of 2708 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Siemens (SEM3 Single Phase) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus
Register addressing
the Modbus Address External column gives 4xxxx register numbers (0-based offset = number minus 40001)
Alarm flag registers
one register, bit field, read write
Alarm bit clearing
write 1 to an alarm bit to clear it
Single Phase Monitor block
holds 28 data items in the order listed
Single Phase Monitor block addressing
addressed as Base plus offset
Float 32 values
2 registers

Registers in the map: 1638 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
0Monitor 1 alarm flags word 
1Monitor 2 alarm flags word 
2Monitor 3 alarm flags word 
3Monitor 4 alarm flags word 
4Monitor 5 alarm flags word 
5Monitor 6 alarm flags word 
6Monitor 7 alarm flags word 
7Monitor 8 alarm flags word 
8Monitor 9 alarm flags word 
9Monitor 10 alarm flags word 
10Monitor 11 alarm flags word 
11Monitor 12 alarm flags word 
12Monitor 13 alarm flags word 
13Monitor 14 alarm flags word 
14Monitor 15 alarm flags word 
15Monitor 16 alarm flags word 
16Monitor 17 alarm flags word 
17Monitor 18 alarm flags word 
18Monitor 19 alarm flags word 
19Monitor 20 alarm flags word 
20Monitor 21 alarm flags word 
21Monitor 22 alarm flags word 
22Monitor 23 alarm flags word 
23Monitor 24 alarm flags word 
24Monitor 25 alarm flags word 
25Monitor 26 alarm flags word 
26Monitor 27 alarm flags word 
27Monitor 28 alarm flags word 
28Monitor 29 alarm flags word 
29Monitor 30 alarm flags word 
30Monitor 31 alarm flags word 
31Monitor 32 alarm flags word 
32Monitor 33 alarm flags word 
33Monitor 34 alarm flags word 
34Monitor 35 alarm flags word 
35Monitor 36 alarm flags word 
36Monitor 37 alarm flags word 
37Monitor 38 alarm flags word 
38Monitor 39 alarm flags word 
39Monitor 40 alarm flags word 
40Monitor 41 alarm flags word 
41Monitor 42 alarm flags word 
42Monitor 43 alarm flags word 
43Monitor 44 alarm flags word 
44Monitor 45 alarm flags word 
45Monitor 46 alarm flags word 
46Monitor 47 alarm flags word 
47Monitor 48 alarm flags word 
48Monitor 49 alarm flags word 
49Monitor 50 alarm flags word 

This is not the complete map: 50 of 1638 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Siemens (SEM3 Three Phase) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Register addressing
the Modbus Address External column gives 4xxxx register numbers (0-based offset = number minus 40001)
Alarm flag registers
one register, bit field, read write
Alarm bit clearing
write 1 to an alarm bit to clear it
Monitor data block addressing
addressed as Base plus offset
Monitor data types
Float 32, uint 16, uint 32 or uint 64
Registers per monitor value
2 or 4

Registers in the map: 3400 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
200Monitor 1 alarm flags word 
201Monitor 2 alarm flags word 
202Monitor 3 alarm flags word 
203Monitor 4 alarm flags word 
204Monitor 5 alarm flags word 
205Monitor 6 alarm flags word 
206Monitor 7 alarm flags word 
207Monitor 8 alarm flags word 
208Monitor 9 alarm flags word 
209Monitor 10 alarm flags word 
210Monitor 11 alarm flags word 
211Monitor 12 alarm flags word 
212Monitor 13 alarm flags word 
213Monitor 14 alarm flags word 
214Monitor 15 alarm flags word 
215Monitor 16 alarm flags word 
216Monitor 17 alarm flags word 
217Monitor 18 alarm flags word 
218Monitor 19 alarm flags word 
219Monitor 20 alarm flags word 
220Monitor 21 alarm flags word 
221Monitor 22 alarm flags word 
222Monitor 23 alarm flags word 
223Monitor 24 alarm flags word 
224Monitor 25 alarm flags word 
225Monitor 26 alarm flags word 
226Monitor 27 alarm flags word 
227Monitor 28 alarm flags word 
228Monitor 29 alarm flags word 
229Monitor 30 alarm flags word 
230Monitor 31 alarm flags word 
231Monitor 32 alarm flags word 
232Monitor 33 alarm flags word 
233Monitor 34 alarm flags word 
234Monitor 35 alarm flags word 
235Monitor 36 alarm flags word 
236Monitor 37 alarm flags word 
237Monitor 38 alarm flags word 
238Monitor 39 alarm flags word 
239Monitor 40 alarm flags word 
240Monitor 41 alarm flags word 
241Monitor 42 alarm flags word 
242Monitor 43 alarm flags word 
243Monitor 44 alarm flags word 
244Monitor 45 alarm flags word 
245Monitor 46 alarm flags word 
246Monitor 47 alarm flags word 
247Monitor 48 alarm flags word 
248Monitor 49 alarm flags word 
249Monitor 50 alarm flags word 

This is not the complete map: 50 of 3400 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Siemens (SICAM P) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Register addressing
register addresses are full 4xxxx holding register numbers and the map uses 0-based offsets (40200 = 199)
Measured value size
occupies 2 registers (data type Measured Value)
Access
the registers are write protected
Write rejection
a write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE)

Registers in the map: 132 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
199Overflow voltage L1 N (ov UL1) single 
200Voltage L N (u L1)Vsingle 
202Voltage L N (u L2)Vsingle 
204Voltage L N (u L3)Vsingle 
206Sum of voltages L N (calculated) (u ne)Vsingle 
208Current (i L1)Asingle 
210Current (i L2)Asingle 
212Current (i L3)Asingle 
214Current (i ne)Asingle 
216Voltage L L (u L12)Vsingle 
218Voltage L L (u L23)Vsingle 
220Voltage L L (u L31)Vsingle 
222Voltage sum (u sum)Vsingle 
224Current sum (i sum)Asingle 
226Active power (p L1)Wsingle 
228Active power (p L2)Wsingle 
230Active power (p L3)Wsingle 
232Active power (p)Wsingle 
234Reactive power (q L1)varsingle 
236Reactive power (q L2)varsingle 
238Reactive power (q L3)varsingle 
240Reactive power (q)varsingle 
242Apparent power (s L1)VAsingle 
244Apparent power (s L2)VAsingle 
246Apparent power (s L3)VAsingle 
248Apparent power (s)VAsingle 
250Active factor cos (cos phi L1) single 
252Active factor cos (cos phi L2) single 
254Active factor cos (cos phi L3) single 
256Active factor cos (cos phi) single 
258Power factor (pf L1) single 
260Power factor (pf L2) single 
262Power factor (pf L3) single 
264Power factor (pf) single 
266Phase angle (phi L1)degsingle 
268Phase angle (phi L2)degsingle 
270Phase angle (phi L3)degsingle 
272Phase angle (phi sum)degsingle 
274Frequency (f)Hzsingle 
276Voltage unbalance (asym U)%single 
278Current unbalance (asym I)%single 
280Thd voltage (thdu L1)%single 
282Thd voltage (thdu L2)%single 
284Thd voltage (thdu L3)%single 
286Thd current (thdi L1)%single 
288Thd current (thdi L2)%single 
290Thd current (thdi L3)%single 
292Harmonic voltage, 5th harmonic wave (hu L1 5)%single 
294Harmonic voltage, 5th harmonic wave (hu L2 5)%single 
296Harmonic voltage, 5th harmonic wave (hu L3 5)%single 

This is not the complete map: 50 of 132 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Siemens (Sentron PAC 3100) - MODBUS Registers Map

Connection and addressing notes

Protocol
Modbus
Function codes
0x03 and 0x04 can read all measured variables
Register addressing
the Offset column is used directly as the register offset (first measured value at offset 1)
Float format
occupies 2 registers
Read and write alignment
a read or write must start at the start offset of a value, otherwise the device returns an exception code

Registers in the map: 89 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: double, dword, single.

MODBUS offsetDescriptionUnitsData typeScale
1Voltage a-NVsingle 
3Voltage b-NVsingle 
5Voltage c-NVsingle 
7Voltage a-bVsingle 
9Voltage b-cVsingle 
11Voltage c-aVsingle 
13Current aAsingle 
15Current bAsingle 
17Current cAsingle 
19Apparent power aVAsingle 
21Apparent power bVAsingle 
23Apparent power cVAsingle 
25Active power aWsingle 
27Active power bWsingle 
29Active power cWsingle 
31Reactive power a (VAR1)varsingle 
33Reactive power b (VAR1)varsingle 
35Reactive power c (VAR1)varsingle 
37Neutral currentAsingle 
39FrequencyHzsingle 
47Total apparent powerVAsingle 
49Total active powerWsingle 
51Total reactive power (VAR1)varsingle 
53Total power factor single 
55Maximum voltage a-NVsingle 
57Maximum voltage b-NVsingle 
59Maximum voltage c-NVsingle 
61Max. voltage a-bVsingle 
63Max. voltage b-cVsingle 
65Max. voltage c-aVsingle 
67Maximum current aAsingle 
69Maximum current bAsingle 
71Maximum current cAsingle 
73Maximum apparent power aVAsingle 
75Maximum apparent power bVAsingle 
77Maximum apparent power cVAsingle 
79Maximum active power aWsingle 
81Maximum active power bWsingle 
83Maximum active power cWsingle 
85Max. reactive power a (VAR1)varsingle 
87Max. reactive power b (VAR1)varsingle 
89Max. reactive power c (VAR1)varsingle 
91Max. neutral currentAsingle 
93Max. frequencyHzsingle 
101Max. total apparent powerVAsingle 
103Max. total active powerWsingle 
105Max. total reactive power (VAR1)varsingle 
107Max. total power factor single 
109Minimum voltage a-NVsingle 
111Minimum voltage b-NVsingle 

This is not the complete map: 50 of 89 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Siemens (Sentron PAC 5100,PAC 5200) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Register numbering
register numbers are stated directly (0201 to 0322 for measured values, step 2)
Registers per measured value
2
Access
measured values are write protected
Write rejection
a write attempt is rejected with exception code 03 (ILLEGAL_DATA_VALUE)

Registers in the map: 55 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0201Voltage a-NVsingle 
0203Voltage b-NVsingle 
0205Voltage c-NVsingle 
0207Voltage neutral conductorVsingle 
0209Current aAsingle 
0211Current bAsingle 
0213Current cAsingle 
0215Current neutral conductorAsingle 
0217Voltage a-bVsingle 
0219Voltage b-cVsingle 
0221Voltage c-aVsingle 
0223Mean value of voltage (P-n)Vsingle 
0225Mean value of currentsAsingle 
0227Active power aWsingle 
0229Active power bWsingle 
0231Active power cWsingle 
0233Active powerWsingle 
0235Reactive power avarsingle 
0237Reactive power bvarsingle 
0239Reactive power cvarsingle 
0241Reactive powervarsingle 
0243Apparent power aVAsingle 
0245Apparent power bVAsingle 
0247Apparent power cVAsingle 
0249Apparent powerVAsingle 
0251Active power factor a single 
0253Active power factor b single 
0255Active power factor c single 
0257Active power factor single 
0259Power factor a single 
0261Power factor b single 
0263Power factor c single 
0265Power factor single 
0267Phase angle adegsingle 
0269Phase angle bdegsingle 
0271Phase angle cdegsingle 
0273Phase angledegsingle 
0275Power frequencyHzsingle 
0277Unbalanced voltage%single 
0279Unbalanced current%single 
0293Frequency calculated every 10 s (internal)Hzsingle 
0295Voltage alab THDS single 
0297Voltage bfbc THDS single 
0299Voltage clca THDS single 
0301Current a THDS single 
0303Current b THDS single 
0305Current c THDS single 
0307Angle vab-vbcdegsingle 
0309Angle vab-vcadegsingle 
0311Angle la-lbdegsingle 

This is not the complete map: 50 of 55 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.