Socomec Countis E24 data logging. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
9999SOCO string(8)
10003Product order ID (Countis:100, protection:200, atys:300, diris:400) word
10004Product ID word
10005JBUS table version word
10006Product software version word
10009Serial_order word
10010Serial_Reserve dword
10017Product version (Major) word
10018Product version (Minor) word
10019Product version (Revision) word
10020Product version (Build) word
10024Software technical base version (Major) word
10025Software technical base version (Minor) word
10026Software technical base version (Revision) word
10027Customization version (Major) word
10028Customization version (Minor) word
10029Product VLO string(8)
10033Customization VLO string(8)
10037Software technical base VLO string(8)
10041Vendor name string(16)
10049Product name string(16)
10057Extended name string(16)
10513Phase to phase voltage: U12V / 100dword
10515Phase to phase voltage: U23V / 100dword
10517Phase to phase voltage: U31V / 100dword
10519Simple voltage: V1V / 100dword
10521Simple voltage: V2V / 100dword
10523Simple voltage: V3V / 100dword
10527Current: I1A / 1000dword
10529Current: I2A / 1000dword
10531Current: I3A / 1000dword
10533Neutral currentA / 1000dword
10535Active powerW / 0.1integer
10537Reactive powervar / 0.1integer
10539Apparent powerVA / 0.1dword
10541Power factor- / 1000integer
10543Active power phase 1W / 0.1integer
10545Active power phase 2W / 0.1integer
10547Active power phase 3W / 0.1integer
10549Reactive power phase 1var / 0.1integer
10551Reactive power phase 2var / 0.1integer
10553Reactive power phase 3var / 0.1integer
10555Apparent power phase 1VA / 0.1dword
10557Apparent power phase 2VA / 0.1dword
10559Apparent power phase 3VA / 0.1dword
10561Power factor phase 1- / 1000integer
10563Power factor phase 2- / 1000integer
10565Power factor phase 3- / 1000integer
10769Total positive active energy (no resetable)Wh / 0.001dword
10771Total positive reactive energy (no resetable)varh / 0.001dword
There are more MODBUS items for this device. Please, download the program.