SolarEdge (SE5000) data logger. MODBUS registers map.
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
40069 | AC Current | A | word |
40070 | Phase A Current | A | word |
40071 | Phase B Current | A | word |
40072 | Phase C Current | A | word |
40073 | Scale factor [A_SF] | | smallint |
40074 | Phase Voltage AB | V | word |
40075 | Phase Voltage BC | V | word |
40076 | Phase Voltage CA | V | word |
40077 | Phase Voltage AN | V | word |
40078 | Phase Voltage BN | V | word |
40079 | Phase Voltage CN | V | word |
40080 | Scale factor [V_SF] | | smallint |
40081 | AC Power | W | smallint |
40082 | Scale factor [W_SF] | | smallint |
40083 | Line Frequency | Hz | word |
40084 | Scale factor [HZ_SF] | | smallint |
40085 | AC Apparent Power | VA | smallint |
40086 | Scale factor [VA_SF] | | smallint |
40087 | AC Reactive Power | var | smallint |
40088 | Scale factor [VAR_SF] | | smallint |
40089 | AC Power Factor | Pct | smallint |
40090 | Scale factor [PF_SF] | | smallint |
40091 | AC Energy | Wh | dword |
40093 | Scale factor [WH_SF] | | smallint |
40094 | DC Current | A | word |
40095 | Scale factor [DCA_SF] | | smallint |
40096 | DC Voltage | V | word |
40097 | Scale factor [DCV_SF] | | smallint |
40098 | DC Power | W | smallint |
40099 | Scale factor [DCW_SF] | | smallint |
40100 | Cabinet Temperature | C | smallint |
40101 | Heat Sink Temperature | C | smallint |
40102 | Transformer Temperature | C | smallint |
40103 | Other Temperature | C | smallint |
40104 | Scale factor [TMP_SF] | | smallint |
40105 | Enumerated value. Operating state | | word |
40106 | Vendor specific operating state code | | word |
40107 | Bitmask value. Event fields | | dword |
40109 | Reserved for future use | | dword |
40111 | Vendor defined events | | dword |
40113 | Vendor defined events | | dword |
40115 | Vendor defined events | | dword |
40117 | Vendor defined events | | dword |
40121 | Well known value registered with SunSpec for compliance | | utf8(32) |
40137 | Manufacturer specific value (32 chars) | | utf8(32) |
40153 | Manufacturer specific value (16 chars) | | utf8(16) |
40161 | Manufacturer specific value (16 chars) | | utf8(16) |
40169 | Manufacturer specific value (32 chars) | | utf8(32) |
40185 | Modbus device address | | word |
40186 | Force even alignment | | |
There are more MODBUS items for this device. Please, download the program. |
SolarEdge (SE10K) data logging
SolarEdge (SE12.5K) data logging
SolarEdge (SE3000H) data logging
SolarEdge (SE3800) data logging
SolarEdge (SE4000H) data logging
SolarEdge (SE5000) data logging
SolarEdge (SE5000H) data logging
SolarEdge (SE5K) data logging
SolarEdge (SE6000H) data logging
SolarEdge (SE7K) data logging
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.