Chauvin Arnoux MD45, MD100, MEMO P200 MODBUS registers: read online

Connect Chauvin Arnoux to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Chauvin Arnoux logging and read.

Do you not know the meter address? Scan the device address online

Chauvin Arnoux (MD45,MD100) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Function codes
03 read holding registers
Modbus ID register
4003
Baud rate register
4004
Parity register
4011
Word order
Float ABCD

Registers in the map: 41. function 3 (holding registers). byte order big-endian. data types: dword, single, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
16389Protocol version single 
16391Software version single 
16393Hardware version single 
16384Serial number dword 
16386Meter code word 
16395MeterAsmallint 
16397S0 output rateimp/kWhsingle 
16399Combination code smallint 
16400LCD time cyclesword 
16402Current direction word 
16405Error code smallint 
16406Power down counter smallint 
16407Present quadrant smallint 
16413Active status word dword 
20480Voltage single 
20488Grid frequencyHzsingle 
20490CurrentAsingle 
20498Total active powerkWsingle 
20506Total reactive powerkvarsingle 
20514Total apparent powerkVAsingle 
20522Power factor single 
24576Total active energykWhsingle 
24578T1 total active energykWhsingle 
24580T2 total active energykWhsingle 
24588Forward active energykWhsingle 
24590T1 forward active energykWhsingle 
24592T2 forward active energykWhsingle 
24600Reverse active energykWhsingle 
24602T1 reverse active energykWhsingle 
24604T2 reverse active energykWhsingle 
24612Total reactive energykvarhsingle 
24614T1 total reactive energykvarhsingle 
24616T2 total reactive energykvarhsingle 
24624Forward reactive energykvarhsingle 
24626TI forward reactive energykvarhsingle 
24628T2 forward reactive energykvarhsingle 
24636Reverse reactive energykvarhsingle 
24638T1 reverse reactive energykvarhsingle 
24640T2 reverse reactive energykvarhsingle 
24648Tariff smallint 
24649Resettable day counterkWhsingle 

Chauvin Arnoux (MEMO P200) - MODBUS Measurements

Connection and addressing notes

Protocol
Modbus RTU
Data bits
8
RTU framing
8-bit bytes, least significant bit first, 2-byte CRC
Parity options
even, odd, none
Data format
32-bit IEEE 754 floats, big endian byte order (4-3-2-1), most significant register first (default)
Baud rates
2400, 4800, 9600, 19200, 38400
Function 04
reads all parameters
Read length
every read request must ask for an even number of registers

Registers in the map: 121 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0Phase 1 voltage line neutralVsingle 
2Phase 2 voltage line neutralVsingle 
4Phase 3 voltage line neutralVsingle 
6Phase 1 currentAsingle 
8Phase 2 currentAsingle 
10Phase 3 currentAsingle 
12Phase 1 active powerWsingle 
14Phase 2 active powerWsingle 
16Phase 3 active pOWCrWsingle 
18Phase 1 apparent powerVAsingle 
20Phase 2 apparent powerVAsingle 
22Phase 3 apparent power (VAsingle 
24Phase 1 reactive powervarsingle 
26Phase 2 reactive powervarsingle 
28Phase 3 reactive powervarsingle 
30Phase 1 power factor single 
32Phase 2 power factor single 
34Phase 3 power factor single 
36Phase 1 phase angledegsingle 
38Phase 2 phase angledegsingle 
40Phase 3 phase angledegsingle 
42Average line neutral voltageVsingle 
46Average line currentAsingle 
48Sum of line currentsAsingle 
52Total system active powerWsingle 
56Total system apparent powerVAsingle 
60Total system reactive powervarsingle 
62Total system power factor single 
66Total system phase angle single 
70FrequencyHzsingle 
72Import active energykWhsingle 
74Export active energykWhsingle 
76Import reactive energykvarhsingle 
78Export reactive energykvarhsingle 
80Total apparent energykVAhsingle 
82Total cumulated currentAhsingle 
84System active power demand total single 
86Max total system active power demand single 
100Total system apparent power demandVAsingle 
102Max total system apparent power demandVAsingle 
104Neutral current demand max neutralAsingle 
106Current demand line to line voltage (Volts)Asingle 
200Line 1 to line 2 voltageVsingle 
202Line 2 to line 3 voltageVsingle 
204Voltage line 3 to line 1Vsingle 
206Voltage average line to lineVsingle 
224Neutral currentAsingle 
234Phase 1 L/N voltage THD%single 
236Phase 2 L/N voltage THD%single 
238Phase 3 L/N voltage THD%single 

This is not the complete map: 50 of 121 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.