Electro Industries Shark - MODBUS Registers Map - Read & Log
The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable Electro Industries Shark logger and capture.
Electro Industries Shark 200 - MODBUS Registers
MODBUS offset
Description
Units
Data type
8
Meter serial number
string(16)
16
Meter type
word
17
Firmware version
string(4)
19
Map version
word
20
Meter configuration
word
21
ASIC version
word
22
Boot firmware version
string(4)
24
Option slot 1 usage
word
25
Option slot 2 usage
word
26
Meter type name
string(16)
278
Volts A-N
dword
279
Volts B-N
dword
280
Volts C-N
dword
281
Volts A-B
dword
282
Volts B-C
dword
283
Volts C-A
dword
284
Amps A
dword
285
Amps B
dword
286
Amps C
dword
287
Neutral current
dword
288
Watts, 3-Ph total
watts
dword
289
VARs, 3-Ph total
dword
290
VAs, 3-Ph total
dword
291
Power factor, 3-Ph total
dword
292
Frequency
dword
293
Watts, phase A
watts
dword
294
Watts, phase B
dword
295
Watts, phase C
dword
296
VARs, phase A
dword
297
VARs, phase B
dword
298
VARs, phase C
dword
299
VAs, phase A
dword
300
VAs, phase B
dword
301
VAs, phase C
dword
302
Power factor, phase A
dword
303
Power factor, phase B
dword
304
Power factor, phase C
dword
999
Volts A-N
dword
1001
Volts B-N
dword
1003
Volts C-N
dword
1005
Volts A-B
dword
1007
Volts B-C
dword
1009
Volts C-A
dword
1011
Amps A
dword
1013
Amps B
dword
1015
Amps C
dword
1017
Watts, 3-Ph total
dword
1019
VARs, 3-Ph total
dword
1021
VAs, 3-Ph total
VAs
single
1023
Power factor, 3-Ph total
single
There are more MODBUS items for this device. Please download the program to discover all registers.
Electro Industries Shark 50 - MODBUS Registers Map
MODBUS offset
Description
Units
Data type
8
Meter serial number
string(16)
16
Meter type
dword
17
Firmware version
dword
19
Map version
dword
20
Meter configuration
dword
21
ASIC version
dword
901
VARs, 3-Ph total
dword
903
VAs, 3-Ph total
dword
1001
Volts B-N
dword
1003
Volts C-N
dword
1005
Volts A-B
dword
1007
Volts B-C
dword
1009
Volts C-A
dword
1011
Amps A
dword
1013
Amps B
dword
1015
Amps C
dword
1017
Watts, 3-Ph total
dword
1019
VARs, 3-Ph total
dword
1021
VAs, 3-Ph total
dword
1023
Power factor, 3-Ph total
dword
1025
Frequency
dword
1027
Neutral current
amps
single
1099
W-hours, received
Wh
integer
1101
W-hours, delivered
Wh
integer
1103
W-hours, net
Wh
integer
1105
W-hours, total
Wh
integer
1107
VAR-hours, positive
integer
1109
VAR-hours, negative
integer
1111
VAR-hours, net
integer
1113
VAR-hours, total
integer
1115
VA-hours, total
integer
1999
Amps a, average
amps
single
2001
Amps b, average
amps
single
2003
Amps c, average
amps
single
2005
Positive watts, 3-Ph, average
watts
single
2007
Positive VARs, 3-Ph, average
VARs
single
2009
Negative watts, 3-Ph, average
watts
single
2011
Negative VARs, 3-Ph, average
VARs
single
2013
VAs, 3-Ph, average
VAs
single
2015
Positive PF, 3-Ph, average
single
2017
Negative PF, 3-PF, average
single
2999
Volts A-N, minimum
volts
single
3001
Volts B-N, minimum
volts
single
3003
Volts C-N, minimum
volts
single
3005
Volts A-B, minimum
volts
single
3007
Volts B-C, minimum
volts
single
3009
Volts C-A, minimum
volts
single
3011
Amps a, minimum avg demand
amps
single
3013
Amps b, minimum avg demand
amps
single
3015
Amps c, minimum avg demand
amps
single
There are more MODBUS items for this device. Please download the program to discover all registers.