Fronius Smart Meter - MODBUS Registers Map - Logging

The data can be automatically logged 24/7 into a database, CSV files, or Excel spreadsheets using the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP) software. These data logging tools provide continuous and reliable Fronius Smart Meter data logger and capture.

Do you not know the meter address? Scan the device address online

Fronius Smart Meter (TS 65A) - MODBUS Registers

MODBUS offset
Description
Units
Data type
258
Voltage
V
dword
260
Voltage Phase Phase
V
dword
262
Active power (sum)
W
dword
264
Apparent power (sum)
VA
dword
266
Reactive power (sum)
var
dword
268
Power factor
 
dword
272
Frequency
HZ
dword
286
Phase A: AC voltage phase 1-2
V
dword
288
Phase A: AC voltage
V
dword
290
Phase A: AC current
ma
dword
292
Phase A: Active power
W
dword
294
Phase A: Apparent power
VA
dword
296
Phase A: Reactive power
var
dword
298
Phase A: Power factor
 
dword
300
Phase B: AC voltage phase 2-3
V
dword
302
Phase B: AC voltage
V
dword
304
Phase B: AC current
ma
dword
306
Phase B: Active power
W
dword
308
Phase B: Apparent power
VA
dword
310
Phase B: Reactive power
var
dword
312
Phase B: Power factor
 
dword
314
Phase C: AC voltage phase 3-1
V
dword
316
Phase C: AC voltage
V
dword
318
Phase C: AC current
ma
dword
320
Phase C: Active power
W
dword
322
Phase C: Apparent power
VA
dword
324
Phase C: Reactive power
var
dword
326
Phase C: Power factor
 
dword
1024
Active energy consumed
kWh
dword
1028
Reactive energy consumed
kvarh
dword
1032
Active energy produced
kWh
dword
1036
Reactive energy produced
kvarh
dword