Garo GNM1D MODBUS registers: read online

Connect Garo to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Garo logging and read.

Do you not know the meter address? Scan the device address online

Garo (GNM1D) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03 read holding, 04 read input
Register addressing
Modicom addresses (300001...) with physical protocol addresses (0000h...)
Physical address
Modicom address minus 300001, 0-based
Data format
INT32 over two registers, INT16 or UINT16
Undefined registers
reading an unlisted address returns an illegal data address exception

Registers in the map: 20. function 4 (input registers). byte order big-endian. data types: integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
770Version code word 
0VL-NVinteger×0.1
2AAinteger×0.001
4WWinteger×0.1
6WAVAinteger×0.1
8Varvar#10integer 
10W dmdWinteger×0.1
12W dmd peakWinteger×0.1
14PFPFsmallint×0.001
15HzHzsmallint×0.1
16kWh (+) TOTkWhinteger×0.1
18Kvarh (TOTkvarhinteger×0.1
20kWh (+) PARTIALkWhinteger×0.1
22Kvarh (+) PARTIALkvarhinteger×0.1
24kWh (+)T1kWhinteger×0.1
26kWh (+) T2kWhinteger×0.1
32kWh (-) TOTkWhinteger×0.1
34Kvarh (-) TOTkvarhinteger×0.1
771Revision codeRevisionword 
11Garo identification code word 

Related MODBUS registers maps