Lumel ND25, ND30 MODBUS registers: read online

Connect Lumel to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Lumel logging and read.

Do you not know the meter address? Scan the device address online

Lumel (ND25) - MODBUS Mapping

Connection and addressing notes

Protocol
Modbus
Function codes
03 read holding registers, 04 read input registers, 16 preset multiple registers
Baud rate options
4800, 9600, 19200, 38400, 57600 bps, user selectable from the front panel
Data format
32-bit IEEE 754 floats, most significant byte first
Alternative byte order
least significant byte first
Register addressing
3X and 4X references
Response timeout
300 ms before retrying

Registers in the map: 102 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
0V1 single 
2V2 single 
4V3 single 
6I1 single 
8I2 single 
10I3 single 
12W1 single 
14W2 single 
16W3 single 
18VA1 single 
20VA2 single 
22VA3 single 
24VAR1 single 
26VAR2 single 
28VAR3 single 
30PF1 single 
32PF2 single 
34PF3 single 
36Angle1 single 
38Angle2 single 
40Angle3 single 
42Volt avg single 
44Volt sum single 
46Current avg single 
48Current sum single 
50Watt avg single 
52Watt sum single 
54VA avg single 
56VA sum single 
58VAr avg single 
60VAr sum single 
62PF avg single 
64PF sum single 
66Phase angle avg single 
68Phase angle sum single 
70Freg single 
72Wh import single 
74Wh export single 
76VArh capacitive single 
78VAr inductve single 
80VAh single 
84kWV demand imp single 
86Max kW demand imp single 
88kW exp demand single 
90Max kW exp demand single 
92kVAr cap demand single 
94Max kVAr demand cap single 
96kVAr ind. demand single 
98Max kVAr ind. demand single 
100KVA demand single 

This is not the complete map: 50 of 102 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Lumel (ND30) - MODBUS Registers

Registers in the map: 161 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
6000L1 phase voltageVsingle 
6002L1 phase currentAsingle 
6004L1 phase active_powerWsingle 
6006LIphase reactive_powervarsingle 
6008L1 phase apparent powerVAsingle 
6010L1 phase active power factor single 
6012Tgp factor of L1 phase single 
6014THD U1%single 
6016THD I1 single 
6018L2 phase voltage single 
6022L2 phase current single 
6024L2 phase reactive_powervarsingle 
6026L2 phase apparent powerVAsingle 
6028L2 phase active power factor single 
6030Tg factor of L2 phase single 
6032THD U2%single 
6034THD I2%single 
6036L3 phase voltage single 
6038L3 phase currentAsingle 
6040L3 phase active_powerWsingle 
6042L3_phase_reactive_powervarsingle 
6044L3 phase apparent powerVAsingle 
6046L3 phase active power factor single 
6048Tgp factor of L3 phase single 
6050THD U3%single 
6052THD I3 single 
6054Mean 3-phase voltage single 
6056Mean 3-phase current single 
60583-phase active powerWsingle 
60603-phase reactive powervarsingle 
60623-phase apparent powerVAsingle 
60643-phase active power factor single 
6066Mean tg factor for 3 phases single 
6068THD U mean 3-phase single 
6070THD I mean 3-phase%single 
6072Frequency single 
6074Phase-to-phase_voltage L1-2 single 
6076Phase-to-phase_voltage L2-3 single 
6078Phase-to-phase_voltage L3-1 single 
6080Mean phase-to-phase voltage single 
6082Active power averaged (P demand)Wsingle 
6084Reactive power averaged (S demand)VAsingle 
6086Current averaged (I demand)Asingle 
6088Neutral wire current single 
6090Active 3-phase import energyMWhsingle×100
6092Active 3-phase import energykWhsingle 
6094Active 3-phase export energyMWhsingle×100
6096Active 3-phase export energykWhsingle 
6098Reactive 3-phase inductive energyMvarhsingle×100
6100Reactive 3-phase inductive energykVAr hsingle 

This is not the complete map: 50 of 161 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.