Carlo Gavazzi EM100, ET100, EM111, EM112 MODBUS registers: read online

Connect Carlo Gavazzi to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Carlo Gavazzi data logger and record.

Do you not know the meter address? Scan the device address online

Carlo Gavazzi (EM100,ET100) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03 read, 04 read
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 40. function 4 (input registers). byte order big-endian. data types: integer, smallint.

MODBUS offsetDescriptionUnitsData typeScale
0V L NVinteger×0.1
2AAinteger×0.001
4WWinteger 
6Va integer 
8Varvarinteger×0.1
10WdmdWinteger 
12Wdmd peakWinteger 
14Pf smallint 
15HzHzsmallint 
16Kwh(+) totkWhinteger 
18Kvarh(+) totkvarinteger×0.1
20Kwh(+) partialkWhinteger 
22Kvarh(+) partialkvarinteger×0.1
24Kwh(+) tariff 1kWhinteger 
26Kwh(+) tariff 2kWhinteger 
32Kwh( ) totkWhinteger 
34Kvarh( ) totkvarinteger×0.1
44Hour counter meter integer×0.01
256AAinteger×0.001
258V L NVinteger×0.1
262WWinteger 
264Vat integer 
266Var Zvarinteger×0.1
268Pf Z integer×0.001
272HzHzinteger 
274Kwh(+) totkWhinteger 
276Kvarh(+) totkvarinteger×0.1
278Kwh( ) totkWhinteger 
280Kvarh( ) totkvarinteger×0.1
282KwdmdWinteger 
284Kwdmd peakWinteger 
328Kwh(+) partialkWhinteger 
330Kvarh(+) partialkvarinteger×0.1
338Kwh(+) tariff 1kWhinteger 
340Kwh(+) tariff 2kWhinteger 
342Kwh(+) tariff 3 integer 
336Kwh(+) tariff 4 integer 
346Kwh( ) partial integer 
384Thd( 16h) A integer 
386Chd( 16h)Vinteger 

Carlo Gavazzi (EM111,EM112,ET112) - MODBUS Registers

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03 read, 04 read
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 51 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: int64, integer, smallint.

MODBUS offsetDescriptionUnitsData typeScale
0V L-NVinteger×0.1
2AAinteger×0.001
4WWinteger×0.1
6VAVAinteger×0.1
8Varvarinteger×0.1
10W dmdWinteger×0.1
12W dmd peakWinteger×0.1
14PFPFsmallint×0.001
15HzHzsmallint×0.1
16kWh (+) TOTkWhinteger×0.1
18Kvarh (+) TOTkvarhinteger×0.1
20kWh (+) PARTIALkWhinteger×0.1
22Kvarh (+) PARTIALkvarhinteger×0.1
24kWh (+) T1kWhinteger×0.1
26kWh (+) T2kWhinteger×0.1
32kWh (-) TOTkWhinteger×0.1
34Kvarh (-) TOTkvarhinteger×0.1
44Hour counterhinteger×0.01
256AAinteger×0.001
258V L-NVinteger×0.1
262WWinteger×0.1
264VAVAinteger×0.1
266Varvarinteger×0.1
268PFPFinteger×0.001
272HzHzinteger×0.1
274kWh (+) TOTkWhinteger×0.1
276Kvarh (+) TOTkvarhinteger×0.1
278kWh (-) TOTkWhinteger×0.1
280Kvarh (-) TOTkvarhinteger×0.1
282kW dmdWinteger×0.1
284kW dmd peakWinteger×0.1
328kWh (+) PARTIALkWhinteger×0.1
330Kvarh (+) PARTIALkvarhinteger×0.1
338kWh (+) T1kWhinteger×0.1
340kWh (+) T2kWhinteger×0.1
1024kWh (+) TOT INTeger partkWhinteger 
1026kWh (+) TOT DECimal partkWhinteger×0.001
1028Kvarh (+) TOT INTeger partkvarhinteger 
1030Kvarh (+) TOT DECimal partkvarhinteger×0.001
1032kWh (-) TOT INTeger part integer 
1034kWh (-) TOT DECimal partkWhinteger×0.001
1036Kvarh (-) TOT INTeger partkvarhinteger 
1038Kvarh (-) TOT DECimal partkvarhinteger×0.001
1280kWh (+) TOT int64 
1284Kvarh (+) TOT int64 
1288kWh (+) partial int64 
1292Kvarh (+) partial int64 
1308kWh (-) TOT int64 
1312kWh (-) partial int64 
1316Kvarh (-) TOT int64 

This is not the complete map: 50 of 51 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Carlo Gavazzi EM21 - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 31. function 4 (holding registers). byte order big-endian. data types: integer, smallint.

MODBUS offsetDescriptionUnitsData typeScale
0V l1-nVinteger×0.1
2V l2-nVinteger×0.1
4V l3-nVinteger×0.1
6V l1-l2Vinteger×0.1
8V l2-l3Vinteger×0.1
10V l3-l1Vinteger×0.1
12A l1Ainteger×0.001
14A l2Ainteger×0.001
16A l3Ainteger×0.001
18W l1Winteger×0.1
20W l2Winteger×0.1
22W l3Winteger×0.1
24Va l1VAinteger×0.1
26Va l2VAinteger×0.1
28Va l3VAinteger×0.1
30Var l1varinteger×0.1
32Var l2varinteger×0.1
34Var l3varinteger×0.1
36V l-nVinteger×0.1
38V l-lVinteger×0.1
40WWinteger×0.1
42VaVAinteger×0.1
44Varvarinteger×0.1
46Pf l1 smallint 
47Pf l2 smallint 
48Pf l3 smallint 
49PfPFsmallint×0.001
50Phase sequence smallint 
51Hz smallint 
52Kwh(+) totkWhinteger×0.1
54Kvarh(+) totkvarhinteger×0.1

Carlo Gavazzi (EM24) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 55 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: integer, smallint.

MODBUS offsetDescriptionUnitsData typeScale
0V L1 N integer×0.1
2V L2 N integer×0.1
4V L3 N integer×0.1
6V L1 L2 integer×0.1
8V L2 L3 integer×0.1
10V L3 L1 integer×0.1
12A L1 integer×0.001
14A L2 integer×0.001
16A L3 integer×0.001
18W L1 integer×0.1
20W L2 integer×0.1
22W L3 integer×0.1
24Va L1 integer×0.1
26Va L2 integer×0.1
28Va L3 integer×0.1
30Var L1 integer×0.1
32Var L2 integer×0.1
34Var L3 integer×0.1
36V L N integer×0.1
38V L L integer×0.1
40W integer×0.1
42Va integer×0.1
44Var integer×0.1
46DmdWinteger×0.1
48DmdVAinteger×0.1
50Pf L1 smallint×0.001
51Pf L2 smallint×0.001
52Pf L3 smallint×0.001
53Pf smallint×0.001
54Phase sequence smallint 
55HzHzsmallint×0.1
56Dmd W max integer×0.1
58Dmd va max integer×0.1
60Dmd A max integer×0.001
62Kwh(+) totkWinteger×0.1
64Kvarh(+) totkvarinteger×0.1
66Kwh(+) parkWinteger×0.1
68Kvarh(+) parkvarinteger×0.1
70Kwh(+) L1kWinteger×0.1
72Kwh(+) L2kWinteger×0.1
74Kwh(+) L3kWinteger×0.1
76Kwh(+) T1kWinteger×0.1
78Kwh(+) T2kWinteger×0.1
80Kwh(+) T3kWinteger×0.1
82Kwh(+) T4kWinteger×0.1
84Kvarh(+) T1kvarinteger×0.1
86Kvarh(+) T2kvarinteger×0.1
88Kvarh(+) T3kvarinteger×0.1
90Kvarh(+) T4kvarinteger×0.1
92Kwh( ) totkWinteger×0.1

This is not the complete map: 50 of 55 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Carlo Gavazzi (EM26) - Measurement Data

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 67 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: integer, smallint.

MODBUS offsetDescriptionUnitsData typeScale
0V L1 N integer×0.1
2V L2 N integer×0.1
4V L3 N integer×0.1
6V L1 L2 integer×0.1
8V L2 L3 integer×0.1
10V L3 L1 integer×0.1
12A L1 integer×0.001
14A L2 integer×0.001
16A L3 integer×0.001
18W L1 integer×0.1
20W L2 integer×0.1
22W L3 integer×0.1
24Va L1 integer×0.1
26Va L2 integer×0.1
28Va L3 integer×0.1
30Var L1 integer×0.1
32Var L2 integer×0.1
34Var L3 integer×0.1
36V L N integer×0.1
38V L L integer×0.1
40W integer×0.1
42Va integer×0.1
44Var integer×0.1
46DmdWinteger×0.1
48DmdVAinteger×0.1
50Pf L1 smallint×0.001
51Pf L2 smallint×0.001
52Pf L3 smallint×0.001
53Pf smallint×0.001
54Phase sequence smallint 
55HzHzsmallint×0.1
56Dmd W max integer×0.1
58Dmd va max integer×0.1
60Dmd A max integer×0.001
62Kwh(+) totkWinteger×0.1
64Kvarh(+) totkvarinteger×0.1
66Kwh(+) parkWinteger×0.1
68Kvarh(+) parkvarinteger×0.1
70Kwh(+) L1kWinteger×0.1
72Kwh(+) L2kWinteger×0.1
74Kwh(+) L3kWinteger×0.1
76Kwh(+) T1kWinteger×0.1
78Kwh(+) T2kWinteger×0.1
80Kwh(+) T3kWinteger×0.1
82Kwh(+) T4kWinteger×0.1
84Kvarh(+) T1kvarinteger×0.1
86Kvarh(+) T2kvarinteger×0.1
88Kvarh(+) T3kvarinteger×0.1
90Kvarh(+) T4kvarinteger×0.1
92Kwh( ) totkWinteger×0.1

This is not the complete map: 50 of 67 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Carlo Gavazzi (EM270) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 66 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: integer.

MODBUS offsetDescriptionUnitsData typeScale
0V L1 N integer×0.1
2V L2 N integer×0.1
4V L3 N integer×0.1
6V L1 L2 integer×0.1
8V L2 L3 integer×0.1
10V L3 L1 integer×0.1
12A L1 integer×0.001
14A L2 integer×0.001
16A L3 integer×0.001
18W integer×0.1
20Va integer×0.1
22Var integer×0.1
24Kwh(+)totkWinteger×0.1
26Kvarh(+)totkvarinteger×0.1
28W dmd integer×0.1
30Va dmd integer×0.1
32W maxdmd integer×0.1
34Va maxdmd integer×0.1
268A L1 tcda integer×0.001
270A L2 tcda integer×0.001
272A L3 tcda integer×0.001
274W L1 tcda integer×0.1
276W L2 tcda integer×0.1
278W L3 tcda integer×0.1
280W tot tcda integer×0.1
282Va tot tcda integer×0.1
284Var tot tcda integer×0.1
286Kwh(+)tcda totkWinteger×0.1
288Kvarh (+)tcda totkvarinteger×0.1
290W tot tcda dmd integer×0.1
292Va tot tcda dmd integer×0.1
294W tot tcda maxdmd integer×0.1
296Va tot tcda maxdmd integer×0.1
298Kwh(+) L1 tcdakWinteger×0.1
300Kwh(+) L2 tcda integer×0.1
302Kwh(+) L3 tcda integer×0.1
304W L1 tcda dmd integer×0.1
306W L2 tcda dmd integer×0.1
308W L3 tcda dmd integer×0.1
310W L1 tcda maxdmd integer×0.1
312W L2 tcda maxdmd integer×0.1
314W L3 tcda maxdmd integer×0.1
524A L1 tcdb integer×0.001
526A L2 tcdb integer×0.001
528A L3 tcdb integer×0.001
530W L1 tcdb integer×0.1
532W L2 tcdb integer×0.1
534W L3 tcdb integer×0.1
536W tot tcdb integer×0.1
538Va tot tcdb integer×0.1

This is not the complete map: 50 of 66 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Carlo Gavazzi (EM271) - MODBUS Values

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 66 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: integer.

MODBUS offsetDescriptionUnitsData typeScale
0V L1 N integer×0.1
2V L2 N integer×0.1
4V L3 N integer×0.1
6V L1 L2 integer×0.1
8V L2 L3 integer×0.1
10V L3 L1 integer×0.1
12A L1 integer×0.001
14A L2 integer×0.001
16A L3 integer×0.001
18W integer×0.1
20Va integer×0.1
22Var integer×0.1
24Kwh(+)totkWinteger×0.1
26Kvarh(+)totkvarinteger×0.1
28W dmd integer×0.1
30Va dmd integer×0.1
32W maxdmd integer×0.1
34Va maxdmd integer×0.1
268A L1 tcda1 integer×0.001
270A L2 tcda1 integer×0.001
272A L3 tcda1 integer×0.001
274W L1 tcda1 integer×0.1
276W L2 tcda1 integer×0.1
278W L3 tcda1 integer×0.1
280W tot tcda1 integer×0.1
282Va tot tcda1 integer×0.1
284Var tot tcda1 integer×0.1
286Kwh(+)tcda1 totkWinteger×0.1
288Kvarh (+)tcda1 totkvarinteger×0.1
290W tot tcda1 dmd integer×0.1
292Va tot tcda1 dmd integer×0.1
294W tot tcda1 maxdmd integer×0.1
296Va tot tcda1 maxdmd integer×0.1
298Kwh(+) L1 tcda1kWinteger×0.1
300Kwh(+) L2 tcda1kWinteger×0.1
302Kwh(+) L3 tcda1kWinteger×0.1
304W L1 tcda1 dmd integer×0.1
306W L2 tcda1 dmd integer×0.1
308W L3 tcda1 dmd integer×0.1
310W L1 tcda1 maxdmd integer×0.1
312W L2 tcda1 maxdmd integer×0.1
314W L3 tcda1 maxdmd integer×0.1
524A L1 tcda2 integer×0.001
526A L2 tcda2 integer×0.001
528A L3 tcda2 integer×0.001
530W L1 tcda2 integer×0.1
532W L2 tcda2 integer×0.1
534W L3 tcda2 integer×0.1
536W tot tcda2 integer×0.1
538Va tot tcda2 integer×0.1

This is not the complete map: 50 of 66 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Carlo Gavazzi (EM300,ET300) - MODBUS Maps

Connection and addressing notes

Protocol
Modbus
Access
read only
Function codes
03, 04
Register addressing
table lists Modicom address (1-based) and physical address (0-based hex)

Registers in the map: 122 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 4 (input registers). byte order big-endian. data types: integer, smallint, word.

MODBUS offsetDescriptionUnitsData typeScale
770Version code word 
771Revision codeRevisionword 
11Carlo Gavazzi Controls identification code word 
0V L1 NVinteger×0.1
2V L2 NVinteger×0.1
4V L3 NVinteger×0.1
6V L1 L2Vinteger×0.1
8V L2 L3Vinteger×0.1
10V L3 L1Vinteger×0.1
12A L1Ainteger×0.001
14A L2Ainteger×0.001
16A L3Ainteger×0.001
18Kw L1Winteger×0.1
20Kw L2Winteger×0.1
22Kw L3Winteger×0.1
24Kva L1 integer×0.1
26Kva L2 integer×0.1
28Kva L3 integer×0.1
30Kvar L1varinteger×0.1
32Kvar L2varinteger×0.1
34Kvar L3varinteger×0.1
36V L N sysVinteger×0.1
38V L L sysVinteger×0.1
40Kw sysWinteger×0.1
42Kva sys integer 
44Kvar sysvarinteger×0.1
46Pf L1 smallint×0.001
47Pf L2 smallint×0.001
48Pf L3 smallint×0.001
49Pf sys smallint×0.001
50Phase sequence smallint 
51HzHzsmallint×0.1
52Kwh (+) totkWhinteger×0.1
54Kvarh (+) totkvarinteger 
56Kw dmdWinteger×0.1
58Kw dmd peakWinteger×0.1
60Kwh (+) partialkWhinteger×0.1
62Kvarh (+) partialkvarinteger×0.1
64Kwh (+) L1kWhinteger×0.1
66Kwh (+) L2kWhinteger×0.1
68Kwh (+) L3kWhinteger×0.1
70Kwh (+) t1kWhinteger×0.1
72Kwh (+) t2kWhinteger×0.1
74Kwh (+) t3kWhinteger 
76Kwh (+) t4kWhinteger×0.1
78Kwh ( ) totkWhinteger×0.1
80Kvarh ( ) totkvarinteger 
90Hour meter integer×0.01
96Kwh ( ) L1kWhinteger×0.1
98Kwh ( ) L2kWhinteger×0.1

This is not the complete map: 50 of 122 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.