MODBUS offsetDescriptionUnitsData type
4096Phase 1 : phase voltageVdword
4098Phase 2 : phase voltageVdword
4100Phase 3 : phase voltageVdword
4102Phase 1 : currentAdword
4104Phase 2 : currentAdword
4106Phase 3 : currentAdword
4108Neutral currentAdword
4110Chained voltage : L1 L2Vdword
4112Chained voltage : L2 L3Vdword
4114Chained voltage : L3 L1Vdword
41163 phase : active powerW/var/VAdword
41183 phase : reactive powerW/var/VAdword
41203 phase : apparent powerW/var/VAdword
41223 phase : sign of active power word
41233 phase : sign of reactive power word
41243 phase : positive active energyWhdword
41263 phase : positive reactive energyWhdword
41283 phase : negative active energyWhdword
41303 phase : negative reactive energyWhdword
41323 phase : power factorssmallint
41333 phase : sector of power factor (cap or ind)aword
4134FrequencyHzword
41353 phase : average powerW/var/VAdword
41373 phase : peak maximum demandW/var/VAdword
4139Time counter for average powerminutesword
4140Phase 1 : active powerW/var/VAdword
4142Phase 2 : active powerW/var/VAdword
4144Phase 3 : active powerW/var/VAdword
4146Phase 1 : sign of active power word
4147Phase 2 : sign of active power word
4148Phase 3 : sign of active power word
4149Phase 1 : reactive powerW/var/VAdword
4151Phase 2 : reactive powerW/var/VAdword
4153Phase 3 : reactive powerW/var/VAdword
4155Phase 1 : sign of reactive power word
4156Phase 2 : sign of reactive power word
4157Phase 3 : sign of reactive power word
4158Phase 1 : apparent powerW/var/VAdword
4160Phase 2 : apparent powerW/var/VAdword
4162Phase 3 : apparent powerW/var/VAdword
4164Phase 1 : power factorssmallint
4165Phase 2 : power factorssmallint
4166Phase 3 : power factorssmallint
4167Phase 1 : power factor sectoraword
4168Phase 2 : power factor sectoraword
4169Phase 3 : power factor sectoraword
4170Phase 1 : thd V1%word
4171Phase 2 : thd V2%word
4172Phase 3 : thd V3%word
4173Phase 1 : thd I1%word
4174Phase 2 : thd I2%word
4175Phase 3 : thd I3%word
4176Phase 1 : I1 averageAdword
4178Phase 2 : I2 averageAdword
4180Phase 3 : I3 averageAdword
4182Phase 1 : I1 peak maximumAdword
4184Phase 2 : I2 peak maximumAdword
4186Phase 3 : I3 peak maximumAdword
4188(i1+i2+i3)/3Adword
4190Phase 1 : V1 minVdword
4192Phase 2 : V2 minVdword
4194Phase 3 : V3 minVdword
4196Phase 1 : V1 maxVdword
4198Phase 2 : V2 maxVdword
4200Phase 3 : V3 maxVdword
42023 phase : active partial energyWhdword
42043 phase : reactive partial energyWhdword
4206Run hour meter word
4207Output relay status(2)word
42083 phase : active average powerW/var/VAdword
42103 phase : reactive average powerW/var/VAdword
42123 phase : apparent average powerW/var/VAdword
42143 phase : active pmd powerW/var/VAdword
42163 phase : reactive pmd powerW/var/VAdword
42183 phase : apparent pmd powerW/var/VAdword
4220Run hour meterminutesdword
4608Current transformer ratio (kta) word
4609Voltage transformer ratio (ktv)sword
4610Future developments dword
4612Device identifier word
4613Future developments word
4614Rfu word
46883 phase positive total active energyWhdword
46903 phase positive total reactive energyWhdword
46923 phase negative total active energyWhdword
46943 phase negative total reactive energyWhdword
46963 phase positive partial active energy tariff 1 active energy (if option tariffs)Whdword
46983 phase negative partial active energy tariff 2 active energy (if option tariffs)Whdword
47003 phase positive partial reactive energy tariff 3 active energy (if option tariffs)Whdword
47023 phase negative partial reactive energy tariff 4 active energy (if option tariffs)Whdword
5376Positive active energy low dword
5378Positive active energy high dword
5380Positive reactive energy lowvdword
5382Positive reactive energy highMvdword
5384Negative active energy low dword
5386Negative active energy high dword
5388Negative reactive energy lowvdword
5390Negative reactive energy highMvdword
5392Partial active energy low dword
5394Partial active energy high dword
There are more MODBUS items for this device. Please, download the program.