Connection and addressing notes
- Protocol
- Modbus
- Default baud rate
- 9600 bps
- Baud rate register
- 40029, 0 = 2400, 1 = 4800, 2 = 9600 (default), 3 = 19200, 4 = 38400
- Stop bits
- 1
- Parity
- none
- Default device address
- 1
- Default password
- 1000
- Network port settings
- take effect after a restart
- Parity and stop bits register
- 40019, 0 = no parity with 1 stop bit (default), 1 = even parity with 1 stop bit, 2 = odd parity with 1 stop bit, 3 = no parity with 2 stop bits
- Address register
- 40021, range 1-247
- Input registers
- 30001 and up hold measured values
- Holding registers
- 40001 and up hold settings
- Function codes
- 03 read, 16 write one parameter per message
- Float register order
- normal = most significant register first, reversed = least significant register first
- Float register order register
- 40041, write 2141 to set the order
- Register 13 description
- default password 0000
- Password chapter
- default password 1000
Registers in the map: 71 (the first 66 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). function 4 (input registers). byte order big-endian. data types: dword.
| MODBUS offset | Description | Units | Data type | Scale |
|---|---|---|---|---|
| 42 | Serial number hi | dword | ||
| 44 | Serial number lo | dword | ||
| 0 | Demand time | dword | ||
| 2 | Demand period | dword | ||
| 6 | System | V | dword | |
| 8 | System current | dword | ||
| 10 | System type | dword | ||
| 12 | Relay pulse width | dword | ||
| 20 | Network node | dword | ||
| 22 | Pulse divisor | dword | ||
| 30 | Energy units prefix | dword | ||
| 36 | System power | dword | ||
| 40 | Register order | dword | ||
| 86 | Relayl energy type | dword | ||
| 88 | Relay2 energy type | dword | ||
| 216 | Reset logged data | dword | ||
| 4 | Phase 3 line to neutral | V | dword | |
| 14 | Phase 2 power | W | dword | |
| 16 | Phase 3 power | W | dword | |
| 18 | Phase 1 | VA | dword | |
| 24 | Phase 1 reactive power | var | dword | |
| 26 | Phase 2 reactive power | var | dword | |
| 28 | Phase 3 reactive power | var | dword | |
| 32 | Phase 2 power factor (1) | dword | ||
| 34 | Phase 3 power factor (1) | dword | ||
| 38 | Phase 2 phase angle | deg | dword | |
| 46 | Average line current | A | dword | |
| 48 | Sum of line currents | A | dword | |
| 52 | Total system power | W | dword | |
| 56 | Total system | VA | dword | |
| 60 | Total system | var | dword | |
| 62 | Total system power factor (1) | dword | ||
| 66 | Total system phase angle | deg | dword | |
| 70 | Frequency of supply voltages | Hz | dword | |
| 72 | Import wh since last reset (2) | kWh/MWh | dword | |
| 74 | Export wh since last reset (2) | kWh/MWh | dword | |
| 76 | Import VArh since last reset (2) | kvarh/MVArh | dword | |
| 78 | Export VArh since last reset (2) | kvarh/MVArh | dword | |
| 80 | VAh since last reset (2) | kVAh/MVAh | dword | |
| 82 | Ah since last reset (3) | Ah/kAh | dword | |
| 84 | Total system power demand (4) | W | dword | |
| 100 | Total system VA demand | VA | dword | |
| 102 | Maximum total system VA demand | VA | dword | |
| 104 | Neutral current demand | A | dword | |
| 106 | Maximum neutral current demand | A | dword | |
| 200 | Line 1 to line 2 | V | dword | |
| 202 | Line 2 to line 3 | V | dword | |
| 204 | Line 3 to line 1 | V | dword | |
| 206 | Average line to line | V | dword | |
| 224 | Neutral current | A | dword | |
| 234 | Phase 1 L/N volts THD | % | dword | |
| 236 | Phase 2 L/N volts THD | % | dword | |
| 238 | Phase 3 L/N volts THD | % | dword | |
| 240 | Phase 1 current THD | % | dword | |
| 242 | Phase 2 current THD | % | dword | |
| 244 | Phase 3 current THD | % | dword | |
| 248 | Average line to neutral volts THD | % | dword | |
| 250 | Average line current THD | % | dword | |
| 254 | -Total system power factor (5) | deg | dword | |
| 258 | Phase 1 current demand | A | dword | |
| 260 | Phase 2 current demand | A | dword | |
| 262 | Phase 3 current demand | A | dword | |
| 264 | Maximum phase 1 current demand | A | dword | |
| 266 | Maximum phase 2 current demand | A | dword | |
| 268 | Maximum phase 3 current demand | A | dword | |
| 334 | Line 1 to line 2 volts THD | % | dword |
This is not the complete map: 66 of 71 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.