Socomec Countis E04 data logging - MODBUS registers map
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset
Description
Units
Data type
10003
Product order ID (Countis:100, protection:200, atys:300, diris:400)
word
10005
JBUS table version
word
10006
Product software version
word
10010
Serial_Reserve
dword
10017
Product version (Major)
word
10018
Product version (Minor)
word
10019
Product version (Revision)
word
10020
Product version (Build)
word
10024
Software technical base version (Major)
word
10025
Software technical base version (Minor)
word
10026
Software technical base version (Revision)
word
10027
Customization version (Major)
word
10028
Customization version (Minor)
word
10029
Product VLO
string(8)
10033
Customization VLO
string(8)
10037
Software technical base VLO
string(8)
10041
Vendor name
string(16)
10049
Product name
string(16)
10057
Extended name
string(16)
10519
Simple voltage: V1
V / 100
dword
10527
Current: I1
A / 1000
dword
10533
Neutral current
A / 1000
dword
10535
Active power
W / 0.1
integer
10537
Reactive power
var / 0.1
integer
10539
Apparent power
VA / 0.1
dword
10541
Power factor
- / 1000
integer
10543
Active power phase 1
W / 0.1
integer
10549
Reactive power phase 1
var / 0.1
integer
10555
Apparent power phase 1
VA / 0.1
dword
10561
Power factor phase 1
- / 1000
integer
10769
Total positive active energy (no resetable)
Wh / 0.001
dword
10945
Total positive active energy (no resetable)
Wh / 0.1
dword
6864
RS485 address: 1 - 247
word
6865
RS485 baud rate: 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400
word
6866
RS485 parity: 0: no parity 1: odd 2: even
word
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.