Connect Socomec to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Socomec logging and read.
Registers in the map: 60 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, string(16), string(8), word.
MODBUS offset
Description
Units
Data type
Scale
50007
Product software version
word
50018
Product version (Major)
word
50019
Product version (Minor)
word
50020
Product version (Revision)
word
50021
Product version (Build)
word
50025
Software technical base version (Major)
word
50026
Software technical base version (Minor)
word
50027
Software technical base version (Revision)
word
50028
Customization version (Major)
word
50029
Customization version (Minor)
word
50000
Product name
string(8)
50004
Product order ID (Countis:100, protection:200, atys:300, diris:400)
word
50005
Product ID
word
50030
Product VLO
string(8)
50034
Customization VLO
string(8)
50038
Software technical base VLO
string(8)
50042
Vendor name
string(16)
50050
Product name
string(16)
50058
Extended name
string(16)
50520
Simple voltage: V1
dword
×0.01
50528
Current: I1
dword
×0.001
50536
Active power +/-: P
integer
×10
50538
Reactive power +/-: Q
integer
×10
50540
Apparent power: S
dword
×10
50542
Power factor: -: leading et +: lagging
PF
integer
×0.001
50544
Active power phase 1 +/-: P1
integer
×10
50550
Reactive power phase 1 +/-: Q1
integer
×10
50556
Apparent power phase 1: S1
dword
×10
50562
Power factor phase 1 -: leading and +: lagging: PF1
integer
×0.001
50770
Total positive active energy (no resetable): ea+
dword
×1000
50772
Total positive reactive energy (no resetable): er +
dword
×1000
50776
Total negative active energy (no resetable): ea-
dword
×1000
50780
Partial positive active energy: ea+
dword
×1000
50782
Partial positive reactive energy: er +
dword
×1000
50786
Partial negative active energy: ea-
dword
×1000
50946
Total positive active energy (no resetable): ea+
dword
×10
50948
Total positive reactive energy (no resetable): er +
dword
×10
50952
Total negative active energy (no resetable): ea-
dword
×10
50956
Partial positive active energy: ea+
dword
×10
50958
Partial positive reactive energy: er +
dword
×10
50962
Partial negative active energy: ea-
dword
×10
51281
Phase to phase voltage: U12
word
×0.01
51282
Phase to phase voltage: U23
word
×0.01
51283
Phase to phase voltage: U31
word
×0.01
51284
Simple voltage: V1
word
×0.01
51285
Simple voltage: V2
word
×0.01
51286
Simple voltage: V3
word
×0.01
51295
Power factor: -: leading and +: lagging
PF
smallint
×0.001
51311
Total positive active energy (no resetable): ea+
word
51312
Total positive reactive energy (no resetable): er +
word
This is not the complete map: 50 of 60 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 60 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, string(16), string(8), word.
MODBUS offset
Description
Units
Data type
Scale
50007
Product software version
word
50018
Product version (Major)
word
50019
Product version (Minor)
word
50020
Product version (Revision)
word
50021
Product version (Build)
word
50025
Software technical base version (Major)
word
50026
Software technical base version (Minor)
word
50027
Software technical base version (Revision)
word
50028
Customization version (Major)
word
50029
Customization version (Minor)
word
50000
Product name
string(8)
50004
Product order ID (Countis:100, protection:200, atys:300, diris:400)
word
50005
Product ID
word
50030
Product VLO
string(8)
50034
Customization VLO
string(8)
50038
Software technical base VLO
string(8)
50042
Vendor name
string(16)
50050
Product name
string(16)
50058
Extended name
string(16)
50520
Simple voltage: V1
dword
×0.01
50528
Current: I1
dword
×0.001
50536
Active power +/-: P
integer
×10
50538
Reactive power +/-: Q
integer
×10
50540
Apparent power: S
dword
×10
50542
Power factor: -: leading et +: lagging
PF
integer
×0.001
50544
Active power phase 1 +/-: P1
integer
×10
50550
Reactive power phase 1 +/-: Q1
integer
×10
50556
Apparent power phase 1: S1
dword
×10
50562
Power factor phase 1 -: leading and +: lagging: PF1
integer
×0.001
50770
Total positive active energy (no resetable): ea+
dword
×1000
50772
Total positive reactive energy (no resetable): er +
dword
×1000
50776
Total negative active energy (no resetable): ea-
dword
×1000
50780
Partial positive active energy: ea+
dword
×1000
50782
Partial positive reactive energy: er +
dword
×1000
50786
Partial negative active energy: ea-
dword
×1000
50946
Total positive active energy (no resetable): ea+
dword
×10
50948
Total positive reactive energy (no resetable): er +
dword
×10
50952
Total negative active energy (no resetable): ea-
dword
×10
50956
Partial positive active energy: ea+
dword
×10
50958
Partial positive reactive energy: er +
dword
×10
50962
Partial negative active energy: ea-
dword
×10
51281
Phase to phase voltage: U12
word
×0.01
51282
Phase to phase voltage: U23
word
×0.01
51283
Phase to phase voltage: U31
word
×0.01
51284
Simple voltage: V1
word
×0.01
51285
Simple voltage: V2
word
×0.01
51286
Simple voltage: V3
word
×0.01
51295
Power factor: -: leading and +: lagging
PF
smallint
×0.001
51311
Total positive active energy (no resetable): ea+
word
51312
Total positive reactive energy (no resetable): er +
word
This is not the complete map: 50 of 60 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 87 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, integer, smallint, string(16), string(8), word.
MODBUS offset
Description
Units
Data type
Scale
50007
Product software version
word
50018
Product version (Major)
word
50019
Product version (Minor)
word
50020
Product version (Revision)
word
50021
Product version (Build)
word
50025
Software technical base version (Major)
word
50026
Software technical base version (Minor)
word
50027
Software technical base version (Revision)
word
50028
Customization version (Major)
word
50029
Customization version (Minor)
word
50000
Product name
string(8)
50004
Product order ID (Countis:100, protection:200, atys:300, diris:400)
word
50005
Product ID
word
50030
Product VLO
string(8)
50034
Customization VLO
string(8)
50038
Software technical base VLO
string(8)
50042
Vendor name
string(16)
50050
Product name
string(16)
50058
Extended name
string(16)
50514
Phase to phase voltage: U12
dword
×0.01
50516
Phase to phase voltage: U23
dword
×0.01
50518
Phase to phase voltage: U31
dword
×0.01
50520
Simple voltage: V1
dword
×0.01
50522
Simple voltage: V2
dword
×0.01
50524
Simple voltage: V3
dword
×0.01
50528
Current: I1
dword
×0.001
50530
Current: I2
dword
×0.001
50532
Current: I3
dword
×0.001
50534
Neutral current: in
dword
×0.001
50536
Active power +/-: P
integer
×10
50538
Reactive power +/-: Q
integer
×10
50540
Apparent power: S
dword
×10
50542
Power factor: -: leading et +: lagging
PF
integer
×0.001
50544
Active power phase 1 +/-: P1
integer
×10
50546
Active power phase 2 +/-: P2
integer
×10
50548
Active power phase 3 +/-: P3
integer
×10
50550
Reactive power phase 1 +/-: Q1
integer
×10
50552
Reactive power phase 2 +/-: Q2
integer
×10
50554
Reactive power phase 3 +/-: Q3
integer
×10
50556
Apparent power phase 1: S1
dword
×10
50558
Apparent power phase 2: S2
dword
×10
50560
Apparent power phase 3: S3
dword
×10
50562
Power factor phase 1 -: leading and +: lagging: PF1
integer
×0.001
50564
Power factor phase 2 -: leading and +: lagging: PF2
integer
×0.001
50566
Power factor phase 3 -: leading and +: lagging: PF3
integer
×0.001
50770
Total positive active energy (no resetable): ea+
dword
×1000
50772
Total positive reactive energy (no resetable): er +
dword
×1000
50776
Total negative active energy (no resetable): ea-
dword
×1000
50780
Partial positive active energy: ea+
dword
×1000
50782
Partial positive reactive energy: er +
dword
×1000
This is not the complete map: 50 of 87 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 558 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: byte, dword, integer, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
18433
Inst. Measurement. Load #1. Date of last instance
s
dword
18435
Inst. Measurement. Load #1. Integration time
s
word
×0.2
18442
Inst. Measurement. Load #1. Frequency
Hz
dword
×0.001
18444
Inst. Measurement. Load #1. Ph N voltage : V1
V
dword
×0.01
18446
Inst. Measurement. Load #1. Ph N voltage : V2
V
dword
×0.01
18448
Inst. Measurement. Load #1. Ph N voltage : V3
V
dword
×0.01
18452
Inst. Measurement. Load #1. Ph ph voltage : U12
V
dword
×0.01
18454
Inst. Measurement. Load #1. Ph ph voltage : U23
V
dword
×0.01
18456
Inst. Measurement. Load #1. Ph ph voltage : U31
V
dword
×0.01
18458
Inst. Measurement. Load #1. Current : I1
A
dword
×0.001
18460
Inst. Measurement. Load #1. Current : I2
A
dword
×0.001
18462
Inst. Measurement. Load #1. Current : I3
A
dword
×0.001
18464
Inst. Measurement. Load #1. Current : in
A
dword
×0.001
18474
Inst. Measurement. Load #1. Snom
VA
dword
18476
Inst. Measurement. Load #1. Total active power
W
integer
18478
Inst. Measurement. Load #1. Total reactive power
var
integer
18480
Inst. Measurement. Load #1. Total lagging reactive power
var
integer
18482
Inst. Measurement. Load #1. Total leading reactive power
var
integer
18484
Inst. Measurement. Load #1. Total apparent power
VA
dword
18486
Inst. Measurement. Load #1. Total power factor
smallint
×0.001
18487
Inst. Measurement. Load #1. Total power factor type
byte
20481
Inst. Measurement. Load #2. Date of last instance
s
dword
20483
Inst. Measurement. Load #2. Integration time
s
word
×0.2
20490
Inst. Measurement. Load #2. Frequency
Hz
dword
×0.001
20492
Inst. Measurement. Load #2. Ph N voltage : V1
V
dword
×0.01
20494
Inst. Measurement. Load #2. Ph N voltage : V2
V
dword
×0.01
20496
Inst. Measurement. Load #2. Ph N voltage : V3
V
dword
×0.01
20500
Inst. Measurement. Load #2. Ph ph voltage : U12
V
dword
×0.01
20502
Inst. Measurement. Load #2. Ph ph voltage : U23
V
dword
×0.01
20504
Inst. Measurement. Load #2. Ph ph voltage : U31
V
dword
×0.01
20506
Inst. Measurement. Load #2. Current : I1
A
dword
×0.001
20508
Inst. Measurement. Load #2. Current : I2
A
dword
×0.001
20510
Inst. Measurement. Load #2. Current : I3
A
dword
×0.001
20512
Inst. Measurement. Load #2. Current : in
A
dword
×0.001
20522
Inst. Measurement. Load #2. Snom
VA
dword
20524
Inst. Measurement. Load #2. Total active power
W
integer
20526
Inst. Measurement. Load #2. Total reactive power
var
integer
20528
Inst. Measurement. Load #2. Total lagging reactive power
var
integer
20530
Inst. Measurement. Load #2. Total leading reactive power
var
integer
20532
Inst. Measurement. Load #2. Total apparent power
VA
dword
20534
Inst. Measurement. Load #2. Total power factor
smallint
×0.001
20535
Inst. Measurement. Load #2. Total power factor type
byte
22529
Inst. Measurement. Load #3. Date of last instance
s
dword
22531
Inst. Measurement. Load #3. Integration time
s
word
×0.2
22538
Inst. Measurement. Load #3. Frequency
Hz
dword
×0.001
22540
Inst. Measurement. Load #3. Ph N voltage : V1
V
dword
×0.01
22542
Inst. Measurement. Load #3. Ph N voltage : V2
V
dword
×0.01
22544
Inst. Measurement. Load #3. Ph N voltage : V3
V
dword
×0.01
22548
Inst. Measurement. Load #3. Ph ph voltage : U12
V
dword
×0.01
22550
Inst. Measurement. Load #3. Ph ph voltage : U23
V
dword
×0.01
This is not the complete map: 50 of 558 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 370 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, smallint, word.
MODBUS offset
Description
Units
Data type
Scale
36864
Inst. Measurement. Network. Date of last instance
s
dword
36866
Inst. Measurement. Network. Integration time
s
word
×0.2
36867
Inst. Measurement. Network. System ph N voltage
V
dword
×0.01
36869
Inst. Measurement. Network. System ph ph voltage
V
dword
×0.01
36871
Inst. Measurement. Network. Frequency
Hz
dword
×0.001
36873
Inst. Measurement. Network. Ph N voltage : V1
V
dword
×0.01
36875
Inst. Measurement. Network. Ph N voltage : V2
V
dword
×0.01
36877
Inst. Measurement. Network. Ph N voltage : V3
V
dword
×0.01
36879
Inst. Measurement. Network. Ph N voltage : vn
V
dword
×0.01
36881
Inst. Measurement. Network. Ph ph voltage : U12
V
dword
×0.01
36883
Inst. Measurement. Network. Ph ph voltage : U23
V
dword
×0.01
36885
Inst. Measurement. Network. Ph ph voltage : U31
V
dword
×0.01
36887
Inst. Measurement. Network. Vdir
V
dword
×0.01
36889
Inst. Measurement. Network. Vinv
V
dword
×0.01
36891
Inst. Measurement. Network. Vhom
V
dword
×0.01
36893
Inst. Measurement. Network. Vnb
%
word
×0.01
36894
Inst. Measurement. Network. Udir
V
dword
×0.01
36896
Inst. Measurement. Network. Uinv
V
dword
×0.01
36898
Inst. Measurement. Network. Unb
%
word
×0.01
36899
Inst. Measurement. Network. Vnba
%
word
×0.01
36900
Inst. Measurement. Network. Unba
%
word
×0.01
36992
Avg. Measurement. Network. Date of last instance
s
dword
36994
Avg. Measurement. Network. Integration time
s
word
36995
Avg. Measurement. Network. System ph N voltage
V
dword
×0.01
36997
Avg. Measurement. Network. System ph ph voltage
V
dword
×0.01
36999
Avg. Measurement. Network. Frequency
Hz
dword
×0.001
37001
Avg. Measurement. Network. Ph N voltage : V1
V
dword
×0.01
37003
Avg. Measurement. Network. Ph N voltage : V2
V
dword
×0.01
37005
Avg. Measurement. Network. Ph N voltage : V3
V
dword
×0.01
37007
Avg. Measurement. Network. Ph N voltage : vn
V
dword
×0.01
37009
Avg. Measurement. Network. Ph ph voltage : U12
V
dword
×0.01
37011
Avg. Measurement. Network. Ph ph voltage : U23
V
dword
×0.01
37013
Avg. Measurement. Network. Ph ph voltage : U31
V
dword
×0.01
37015
Avg. Measurement. Network. Vdir
V
dword
×0.01
37017
Avg. Measurement. Network. Vinv
V
dword
×0.01
37019
Avg. Measurement. Network. Vhom
V
dword
×0.01
37021
Avg. Measurement. Network. Vnb
%
word
×0.01
37022
Avg. Measurement. Network. Udir
V
dword
×0.01
37024
Avg. Measurement. Network. Uinv
V
dword
×0.01
37026
Avg. Measurement. Network. Unb
%
word
×0.01
37027
Avg. Measurement. Network. Vnba
%
word
×0.01
37028
Avg. Measurement. Network. Unba
%
word
×0.01
37120
Inst. Fundamental measurement. Network. Date of last instance
s
dword
37122
Inst. Fundamental measurement. Network. Integration time
s
word
×0.2
37123
Inst. Fundamental measurement. Network. Ph N voltage: v1h1
V
dword
×0.01
37125
Inst. Fundamental measurement. Network. Ph N voltage: v2h1
V
dword
×0.01
37127
Inst. Fundamental measurement. Network. Ph N voltage: v3h1
V
dword
×0.01
37129
Inst. Fundamental measurement. Network. Ph N voltage: vnh1
V
dword
×0.01
37131
Inst. Fundamental measurement. Network. Ph N voltage phase: phv1h1
smallint
×0.1
37132
Inst. Fundamental measurement. Network. Ph N voltage phase: phv2h1
smallint
×0.1
This is not the complete map: 50 of 370 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Registers in the map: 711 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: byte, dword, int64, integer, smallint, string, word.
MODBUS offset
Description
Units
Data type
Scale
50004
Product order ID
word
50005
Product ID
word
50006
MODBUS Table Version
word
50007
Product software version
word
50018
Product version (Major)
word
50019
Product version (Minor)
word
50020
Product version (Revision)
word
50021
Product version (Build)
word
50025
Software technical base version (Major)
word
50026
Software technical base version (Minor)
word
50027
Software technical base version (Revision)
word
50028
Customization version (Major)
word
50029
Customization version (Minor)
word
50030
Product VLO
string
50034
Customization VLO
string
50038
Software technical base VLO
string
50050
Product name
string
50058
Extended name
string
50066
Ressource version (Build 2)
word
18433
Inst. Measurement. Load #1. Date of last instance
s
dword
18435
Inst. Measurement. Load #1. Integration time
s
word
×0.2
18442
Inst. Measurement. Load #1. Frequency
Hz
dword
×0.001
18444
Inst. Measurement. Load #1. Ph N voltage : V1
V
dword
×0.01
18446
Inst. Measurement. Load #1. Ph N voltage : V2
V
dword
×0.01
18448
Inst. Measurement. Load #1. Ph N voltage : V3
V
dword
×0.01
18452
Inst. Measurement. Load #1. Ph ph voltage : U12
V
dword
×0.01
18454
Inst. Measurement. Load #1. Ph ph voltage : U23
V
dword
×0.01
18456
Inst. Measurement. Load #1. Ph ph voltage : U31
V
dword
×0.01
18458
Inst. Measurement. Load #1. Current : I1
A
dword
×0.001
18460
Inst. Measurement. Load #1. Current : I2
A
dword
×0.001
18462
Inst. Measurement. Load #1. Current : I3
A
dword
×0.001
18464
Inst. Measurement. Load #1. Current : in
A
dword
×0.001
18474
Inst. Measurement. Load #1. Snom
VA
dword
18476
Inst. Measurement. Load #1. Total active power
W
integer
18478
Inst. Measurement. Load #1. Total reactive power
var
integer
18480
Inst. Measurement. Load #1. Total lagging reactive power
var
integer
18482
Inst. Measurement. Load #1. Total leading reactive power
var
integer
18484
Inst. Measurement. Load #1. Total apparent power
VA
dword
18486
Inst. Measurement. Load #1. Total power factor
smallint
×0.001
18487
Inst. Measurement. Load #1. Total power factor type
byte
20481
Inst. Measurement. Load #2. Date of last instance
s
dword
20483
Inst. Measurement. Load #2. Integration time
s
word
×0.2
20490
Inst. Measurement. Load #2. Frequency
Hz
dword
×0.001
20492
Inst. Measurement. Load #2. Ph N voltage : V1
V
dword
×0.01
20494
Inst. Measurement. Load #2. Ph N voltage : V2
V
dword
×0.01
20496
Inst. Measurement. Load #2. Ph N voltage : V3
V
dword
×0.01
20500
Inst. Measurement. Load #2. Ph ph voltage : U12
V
dword
×0.01
20502
Inst. Measurement. Load #2. Ph ph voltage : U23
V
dword
×0.01
20504
Inst. Measurement. Load #2. Ph ph voltage : U31
V
dword
×0.01
20506
Inst. Measurement. Load #2. Current : I1
A
dword
×0.001
This is not the complete map: 50 of 711 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Socomec (Multis L20, Multis L40) - MODBUS Registers Map
Registers in the map: 114 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, integer, smallint.
MODBUS offset
Description
Units
Data type
Scale
0
Voltage, L1
V
dword
×0.1
2
Voltage, L2
V
dword
×0.1
4
Voltage, L3
V
dword
×0.1
6
Current, L1
A
dword
×0.001
8
Current, L2
A
dword
×0.001
10
Current, L3
A
dword
×0.001
12
Current, L-N
A
dword
×0.001
14
Voltage, L1-L2
V
dword
×0.1
16
Voltage, L2-L3
V
dword
×0.1
18
Voltage, L1-L3
V
dword
×0.1
20
Active power, L1
W
integer
×0.1
22
Active power, L2
W
integer
×0.1
24
Active power, L3
W
integer
×0.1
26
Reactive power, L1
var
integer
×0.1
28
Reactive power, L2
var
integer
×0.1
30
Reactive power, L3
var
integer
×0.1
32
Apparent power, L1
var
dword
×0.1
34
Apparent power, L2
var
dword
×0.1
36
Apparent power, L3
var
dword
×0.1
38
Power factor, L1
integer
×0.001
40
Power factor, L1
integer
×0.001
42
Power factor, L1
integer
×0.001
44
Total import active power
W
integer
×0.1
46
Total export active power
W
integer
×0.1
48
Total inductive reactive power
var
integer
×0.1
50
Total capacitive reactive power
var
integer
×0.1
52
Total apparent power
VA
dword
×0.1
54
Average inductive CosF
var
integer
×0.001
56
Average capacitive CosF
var
integer
×0.001
58
Frequency
Hz
integer
×0.01
60
Voltage angle, L1
deg
dword
×0.001
62
Voltage angle, L2
deg
dword
×0.001
64
Voltage angle, L3
deg
dword
×0.001
66
Current angle, L1
deg
dword
×0.001
68
Current angle, L2
deg
dword
×0.001
70
Current angle, L3
deg
dword
×0.001
84
Digital inputs
dword
86
Import active energy 1
Wh
int64
90
Export active energy 1
Wh
int64
94
Inductive reactive energy 1
varh
int64
98
Capacitive reactive energy 1
varh
int64
102
Import active energy 2
Wh
int64
106
Export active energy 2
Wh
int64
110
Inductive reactive energy 2
varh
int64
114
Capacitive reactive energy 2
varh
int64
118
Voltage, min, L1
V
dword
×0.1
120
Voltage, min, L2
V
dword
×0.1
122
Voltage, min, L3
V
dword
×0.1
124
Voltage, min, L1-L2
V
dword
×0.1
126
Voltage, min, L2-L3
V
dword
×0.1
This is not the complete map: 50 of 114 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.