SolarEdge (SE7K) logger. MODBUS registers map.


This data is being extracted with help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
40069AC CurrentAword
40070Phase A CurrentAword
40071Phase B CurrentAword
40072Phase C CurrentAword
40073Scale factor [A_SF] smallint
40074Phase Voltage ABVword
40075Phase Voltage BCVword
40076Phase Voltage CAVword
40077Phase Voltage ANVword
40078Phase Voltage BNVword
40079Phase Voltage CNVword
40080Scale factor [V_SF] smallint
40081AC PowerWsmallint
40082Scale factor [W_SF] smallint
40083Line FrequencyHzword
40084Scale factor [HZ_SF] smallint
40085AC Apparent PowerVAsmallint
40086Scale factor [VA_SF] smallint
40087AC Reactive Powervarsmallint
40088Scale factor [VAR_SF] smallint
40089AC Power FactorPctsmallint
40090Scale factor [PF_SF] smallint
40091AC EnergyWhdword
40093Scale factor [WH_SF] smallint
40094DC CurrentAword
40095Scale factor [DCA_SF] smallint
40096DC VoltageVword
40097Scale factor [DCV_SF] smallint
40098DC PowerWsmallint
40099Scale factor [DCW_SF] smallint
40100Cabinet TemperatureCsmallint
40101Heat Sink TemperatureCsmallint
40102Transformer TemperatureCsmallint
40103Other TemperatureCsmallint
40104Scale factor [TMP_SF] smallint
40105Enumerated value. Operating state word
40106Vendor specific operating state code word
40107Bitmask value. Event fields dword
40109Reserved for future use dword
40111Vendor defined events dword
40113Vendor defined events dword
40115Vendor defined events dword
40117Vendor defined events dword

SolarEdge (SE7K) data logging