Connect Meatrol to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Meatrol data logging and capture.

Do you not know the meter address? Scan the device address online

Meatrol (ME237) - MODBUS Measurements

Registers in the map: 155 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
1000Voltage value of phase AVsingle 
1002Voltage value of phase BVsingle 
1004Voltage value of phase CVsingle 
1006Average phase voltage valueVsingle 
1008Voltage value of line A-BVsingle 
1010Voltage value of line B-CVsingle 
1012Voltage value of line C-AVsingle 
1014Average line voltage valueVsingle 
1016Current value of phase AAsingle 
1018Current value of phase BAsingle 
1020Current value of phase CAsingle 
1022Average value of three-phase currentAsingle 
1026Active power of phase AWsingle 
1028Active power of phase BWsingle 
1030Active power of phase CWsingle 
1032Sum of three-phase active powerWsingle 
1034Reactive power of phase Avarsingle 
1036Reactive power of phase Bvarsingle 
1038Reactive power of phase Cvarsingle 
1040Sum of three-phase reactive powervarsingle 
1042Apparent power of phase AVAsingle 
1044Apparent power of phase BVAsingle 
1046Apparent power of phase AVAsingle 
1048Sum of three-phase apparent powerVAsingle 
1050Power factor of phase A single 
1052Power factor of phase B single 
1054Power factor of phase C single 
1056Average power factor single 
1058Fundamental power factor of phase A single 
1060Fundamental power factor of phase B single 
1062Fundamental power factor of phase C single 
1064Average fundamental power factor single 
1066Grid frequencyHzsingle 
2000Percentage of total harmonic of voltage of phase A%single 
2002Percentage of total harmonic of voltage of phase B%single 
2004Percentage of total harmonic of voltage of phase A%single 
2006Three phase voltage total harmonic percentage average%single 
2008Percentage of total harmonic current of phase A%single 
2010Percentage of total harmonic current of phase B%single 
2012Percentage of total harmonic current of phase C%single 
2014Percentage average value of total harmonic of three-phase current%single 
4000Positive active energy of phase AkWhdword×0.1
4002Positive active energy of phase BkWhdword×0.1
4004Positive active energy of phase CkWhdword×0.1
4006Sum of three-phase positive active energykWhdword×0.1
4008Reverse active electric energy of phase AkWhdword×0.1
4010Reverse active electric energy of phase BkWhdword×0.1
4012Reverse active electric energy of phase CkWhdword×0.1
4014Sum of three-phase reverse active energykWhdword×0.1
4024Positive reactive energy of phase Akvarhdword×0.1

This is not the complete map: 50 of 155 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Meatrol (ME437) - MODBUS Measurements

Registers in the map: 133 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
2000Phase 1 power factor single 
2002Phase 2 power factor single 
2004Phase 3 power factor single 
2006Average of PF1, PF2, PF3 single 
2008Phase 1 displacement power factor single 
2010Phase 2 displacement power factor single 
2012Phase 3 displacement power factor single 
2014Average of DPF1, DPF2, DPF3 single 
2016Phase 1 frequencyHzsingle 
2018Phase 2 frequencyHzsingle 
2020Phase 3 frequencyHzsingle 
2022Average of freq1, freq2, freq3Hzsingle 
2024Range:2-52 word 
2025Range:2-52 word 
2026Range:2-52 word 
2027Phase 1 X times harmonics current distortion%single 
2029Phase 2 X times harmonics current%single 
2031Phase 3 X times harmonics current distortion%single 
2033Average of I1THDx, I2THDx, I3THDx%single 
2035Phase 1 y times harmonics current distortion%single 
2037Phase 2 y times harmonics current distortion%single 
2039Phase 3 y times harmonics current distortion%single 
2041Average of U1THDy, U2THDy, U3THDy%single 
2043Phase 1 z times harmonics current distortion%single 
2045Phase 2 z times harmonics current distortion%single 
2047Phase 3 z times harmonics current distortion%single 
2049Average of U1THDz, U2THDz, U3THDz%single 
2051Phase 1 total harmonics current distortion%single 
2053Phase 2 total harmonics current distortion%single 
2055Phase 3 total harmonics current distortion%single 
2057Average of U1THD, U2THD, U3THD%single 
2059Phase 1 x times harmonics currentVsingle 
2061Phase 2 x times harmonics currentVsingle 
2063Phase 3 x times harmonics currentVsingle 
2065Average of U1THx, U2THx, U3THxVsingle 
2067Phase 1 y times harmonics currentVsingle 
2069Phase 2 y times harmonics currentVsingle 
2071Phase 3 y times harmonics currentVsingle 
2073Average of U1THy, U2THy, U3THyVsingle 
2075Phase 1 z times harmonics currentVsingle 
2077Phase 2 z times harmonics currentVsingle 
2079Phase 3 z times harmonics currentVsingle 
2081Average of U1THz, U2THz, U3THzVsingle 
2083Phase 1 X times harmonics voltage distortion%single 
2085Phase 2 X times harmonics voltage distortion%single 
2087Phase 3 X times harmonics voltage%single 
2089Average of U1THDx, U2THDx, U3THDx%single 
2091Phase 1 y times harmonics voltage distortion%single 
2093Phase 2 y times harmonics voltage distortion%single 
2095Phase 3 y times harmonics voltage distortion%single 

This is not the complete map: 50 of 133 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Meatrol (ME631) - MODBUS Measurements

Registers in the map: 133 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, single, word.

MODBUS offsetDescriptionUnitsData typeScale
2000Phase 1 power factor single 
2002Phase 2 power factor single 
2004Phase 3 power factor single 
2006Average of PF1, PF2, PF3 single 
2008Phase 1 displacement power factor single 
2010Phase 2 displacement power factor single 
2012Phase 3 displacement power factor single 
2014Average of DPF1, DPF2, DPF3 single 
2016Phase 1 frequencyHzsingle 
2018Phase 2 frequencyHzsingle 
2020Phase 3 frequencyHzsingle 
2022Average of freq1, freq2, freq3Hzsingle 
2024Range:2-52 word 
2025Range:2-52 word 
2026Range:2-52 word 
2027Phase 1 X times harmonics current distortion%single 
2029Phase 2 X times harmonics current distortion%single 
2031Phase 3 X times harmonics current distortion%single 
2033Average of I1THDx, I2THDx, I3THDx%single 
2035Phase 1 y times harmonics current distortion%single 
2037Phase 2 y times harmonics current%single 
2039Phase 3 y times harmonics current distortion%single 
2041Average of U1THDy, U2THDy, U3THDy%single 
2043Phase 1 z times harmonics current distortion%single 
2045Phase 2 z times harmonics current distortion%single 
2047Phase 3 z times harmonics current distortion%single 
2049Average of U1THDz, U2THDz, U3THDz%single 
2051Phase 1 total harmonics current distortion%single 
2053Phase 2 total harmonics current distortion%single 
2055Phase 3 total harmonics current distortion%single 
2057Average of U1THD, U2THD, U3THD%single 
2059Phase 1 x times harmonics currentVsingle 
2061Phase 2 x times harmonics currentVsingle 
2063Phase 3 x times harmonics currentVsingle 
2065Average of U1THx, U2THx, U3THxVsingle 
2067Phase 1 y times harmonics currentVsingle 
2069Phase 2 y times harmonics currentVsingle 
2071Phase 3 y times harmonics currentVsingle 
2073Average of U1THy, U2THy, U3THyVsingle 
2075Phase 1 z times harmonics currentVsingle 
2077Phase 2 z times harmonics currentVsingle 
2079Phase 3 z times harmonics currentVsingle 
2081Average of U1THz, U2THz, U3THzVsingle 
2083Phase 1 X times harmonics voltage distortion%single 
2085Phase 2 X times harmonics voltage distortion%single 
2087Phase 3 X times harmonics voltage distortion%single 
2089Average of U1THDx, U2THDx, U3THDx%single 
2091Phase 1 y times harmonics voltage distortion%single 
2093Phase 2 y times harmonics voltage distortion%single 
2095Phase 3 y times harmonics voltage%single 

This is not the complete map: 50 of 133 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Meatrol (MP440) - Measurement Data

Registers in the map: 216 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: dword, int64, single, word.

MODBUS offsetDescriptionUnitsData typeScale
990 = direct connect 1 = VT word 
102=realvalue*1000Vdword 
1000Current phase AAsingle 
1002Current phase BAsingle 
1004Current phase CAsingle 
1006Current phase NAsingle 
1008Average of IA, IB, ICAsingle 
1010Voltage UA-UNVsingle 
1012Voltage UB-UNVsingle 
1014Voltage UC-UNVsingle 
1016Voltage UN-UEVsingle 
1018Average of UA, UB, UCVsingle 
1020Voltage UA-UBVsingle 
1022Voltage UB-UCVsingle 
1024Voltage UC-UAVsingle 
1026Average of UAB, UBC, UCAVsingle 
1028Active power phase AkWsingle 
1030Active power phase BkWsingle 
1032Active power phase CkWsingle 
1034Total active powerkWsingle 
1036Reactive power phase Akvarsingle 
1038Reactive power phase Bkvarsingle 
1040Reactive power phase Ckvarsingle 
1042Total reactive powerkvarsingle 
1044Apparent power phase AkVAsingle 
1046Apparent power phase BkVAsingle 
1048Apparent power phase CkVAsingle 
1050Total apparent powerkVAsingle 
1052Power factor phase A single 
1054Power factor phase B single 
1056Power factor phase C single 
1058Total power factor single 
1060Displacement power factor phase A single 
1062Displacement power factor phase B single 
1064Displacement power factor phase C single 
1066Total displacement power factor single 
1068Frequency phase AHzsingle 
1070Frequency phase BHzsingle 
1072Frequency phase CHzsingle 
1074Average of FreqA, FreqB, FreqCHzsingle 
2000Active energy import phase AkWhdword 
2002Active energy import phase BkWhdword 
2004Active energy import phase CkWhdword 
2006Total active energy import phase allkWhdword 
2008Active energy export phase AkWhdword 
2010Active energy export phase BkWhdword 
2012Active energy export phase CkWhdword 
2014Total active energy export phase allkWhdword 
2016Reactive energy import phase Akvarhdword 
2018Reactive energy import phase Bkvarhdword 

This is not the complete map: 50 of 216 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.