Phoenix Contact EEM-EM3xx, EM325, EM355 MODBUS registers: read online

Connect Phoenix Contact to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown. For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Phoenix Contact data logging and capture.

Do you not know the meter address? Scan the device address online

Phoenix Contact (EEM-EM3xx,EM325,EM355,EM375,EM327,EM357,EM377) - MODBUS Maps

Connection and addressing notes

Function codes
03 read
Register addressing
decimal and hex (e.g. 4096 = 0x1000)
Data format
32-bit float values occupy 2 registers

Registers in the map: 164 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.

MODBUS offsetDescriptionUnitsData typeScale
4096Conductor voltage to N U1Vsingle 
4098Conductor voltage to N U2Vsingle 
4100Conductor voltage to N U3Vsingle 
4102Conductor voltage to conductor U12Vsingle 
4104Conductor voltage to conductor U23Vsingle 
4106Conductor voltage to conductor U31Vsingle 
4108External conductor voltage systemVsingle 
4110Current in conductor I1Asingle 
4112Current in conductor I2Asingle 
4114Current in conductor I3Asingle 
4116Current in conductor inAsingle 
4118System currentAsingle 
4120Power factor phase 1 +/- single 
4122Power factor phase 2 +/- single 
4124Power factor phase 3 +/- single 
4126System power factor single 
4128Active power phase 1 +/-Wsingle 
4130Active power phase 2 +/-Wsingle 
4132Active power phase 3 +/-Wsingle 
4134Total active power +/-Wsingle 
4136Apparent power phase 1VAsingle 
4138Apparent power phase 2VAsingle 
4140Apparent power phase 3VAsingle 
4142Total apparent power +/-VAsingle 
4144Reactive power phase 1 +/-varsingle 
4146Reactive power phase 2 +/-varsingle 
4148Reactive power phase 3 +/-varsingle 
4150Total reactive power +/-varsingle 
4152FrequencyHzsingle 
4154Phase sequence 0.123 single 
4352Total active energy procurement L1Whsingle 
4354Total active energy procurement L2Whsingle 
4356Total active energy procurement L3Whsingle 
4358Total active energy procurement sumWhsingle 
4360Total active energy supply L1Whsingle 
4362Total active energy supply L2Whsingle 
4364Total active energy supply L3Whsingle 
4366Total active energy supply sumWhsingle 
4368Total inductive apparent energy procurement L1VAhsingle 
4370Total inductive apparent energy procurement L2VAhsingle 
4372Total inductive apparent energy procurement L3VAhsingle 
4376Total inductive apparent energy supply L1VAhsingle 
4378Total inductive apparent energy supply L2VAhsingle 
4380Total inductive apparent energy supply L3VAhsingle 
4382Total inductive apparent energy supply sumVAhsingle 
4384Total capacitive apparent energy procurement L1VAhsingle 
4386Total capacitive apparent energy procurement L2VAhsingle 
4388Total capacitive apparent energy procurement L3VAhsingle 
4390Total capacitive apparent energy procurement sumVAhsingle 
4392Total capacitive apparent energy supply L1VAhsingle 

This is not the complete map: 50 of 164 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.

Phoenix Contact (EEM-MA,EEM-MA3xx) - MODBUS Measurements

Connection and addressing notes

Function codes
03 read
Register addressing
decimal and hex (e.g. 50512 = 0xC550)
Data format
32-bit values occupy 2 registers
Scaling
UInt32 values are scaled by a factor (e.g. factor 100)

Registers in the map: 42. function 3 (holding registers). byte order big-endian. data types: dword, integer.

MODBUS offsetDescriptionUnitsData typeScale
10511Hour: operating hours counterhdword×0.01
10513U12: conductor voltageVdword×0.01
10515U23: conductor voltageVdword×0.01
10517U31: conductor voltageVdword×0.01
10519V1: conductor voltage to NVdword×0.01
10521V2: conductor voltage to NVdword×0.01
10523V3: conductor voltage to NVdword×0.01
10525F: frequencyHzdword×0.01
10527I1: currentAdword×0.001
10529I2: currentAdword×0.001
10531I3: currentAdword×0.001
10533In: neutral conductor currentAdword×0.001
10535P: total active power +/-Winteger×10
10537Q: total reactive power +/-varinteger×10
10539S: total apparent powerVAdword×10
10541PF: total power factor -: capacitive and +: inductive integer×0.001
10543P1: active power phase 1 +/-Winteger×10
10545P2: active power phase 2 +/-Winteger×10
10547P3: active power phase 3 +/-Winteger×10
10549Q1: reactive power phase 1 +/-varinteger×10
10551Q2: reactive power phase 2 +/-varinteger×10
10553Q3: reactive power phase 3 +/-varinteger×10
10555S1: apparent power phase 1VAdword×10
10557S2: apparent power phase 2VAdword×10
10559S3: apparent power phase 3VAdword×10
10561PF1; power factor, phase 1 -: capacitive and +: inductive integer×0.001
10563PF2; power factor, phase 2 -: capacitive and +: inductive integer×0.001
10565PF3; power factor, phase 3 -: capacitive and +: inductive integer×0.001
10567ISYS: mean current valueAdword×0.001
10569USYS: mean value of line voltagesVdword×0.01
10571VSYS: mean value of line voltages to NVdword×0.01
10767Hour: operating hours counterhdword×0.01
10769Total active energy procurement systemkWhdword 
10771Total inductive reactive energy systemkvarhdword 
10773Total apparent energy systemkVAhdword 
10775Total active energy supply systemkWhdword 
10777Total capacitive reactive energy systemkvarhdword 
10779Partial energy meter active energy pro- curement systemkWhdword 
10781Partial energy meter inductive reactive energy systemkvarhdword 
10783Partial energy meter apparent energy systemkVAhdword 
10785Partial energy meter active energy sup- ply systemkWhdword 
10787Partial energy meter capacitive reactive energy systemkvarhdword 

Phoenix Contact (EEM-MA3xx) - MODBUS Values

Connection and addressing notes

Function codes
03 read
Register addressing
decimal and hex (e.g. 50512 = 0xC550)
Data format
32-bit values occupy 2 registers
Scaling
UInt32 values are scaled by a factor (e.g. factor 100)

Registers in the map: 42. function 3 (holding registers). byte order big-endian. data types: dword, integer.

MODBUS offsetDescriptionUnitsData typeScale
50512Hour: operating hours counterhdword×0.01
50514U12: conductor voltageVdword×0.01
50516U23: conductor voltageVdword×0.01
50518U31: conductor voltageVdword×0.01
50520V1: conductor voltage to NVdword×0.01
50522V2: conductor voltage to NVdword×0.01
50524V3: conductor voltage to NVdword×0.01
50526F: frequencyHzdword×0.01
50528I1: currentAdword×0.001
50530I2: currentAdword×0.001
50532I3: currentAdword×0.001
50534In: neutral conductor currentAdword×0.001
50536Sum P: total active power +/-Winteger×10
50538Sum Q: total reactive power +/-varinteger×10
50540Sum S: total apparent powerVAdword×10
50542Sum PF: total power factor -: capacitive and +: inductive integer×0.001
50544P1: active power phase 1 +/-Winteger×10
50546P2: active power phase 2 +/-Winteger×10
50548P3: active power phase 3 +/-Winteger×10
50550Q1: reactive power phase 1 +/-varinteger×10
50552Q2: reactive power phase 2 +/-varinteger×10
50554Q3: reactive power phase 3 +/-varinteger×10
50556S1: apparent power phase 1VAdword×10
50558S2: apparent power phase 2VAdword×10
50560S3: apparent power phase 3VAdword×10
50562PF1; power factor, phase 1 -: capacitive and +: inductive integer×0.001
50564PF2; power factor, phase 2 -: capacitive and +: inductive integer×0.001
50566PF3; power factor, phase 3 -: capacitive and +: inductive integer×0.001
50568ISYS: mean current valueAdword×0.001
50570USYS: mean value of line voltagesVdword×0.01
50572VSYS: mean value of line voltages to NVdword×0.01
50768Hour: operating hours counterhdword×0.01
50770Total active energy procurement systemkWhdword 
50772Total inductive reactive energy systemkvarhdword 
50774Total apparent energy systemkVAhdword 
50776Total active energy supply systemkWhdword 
50778Total capacitive reactive energy systemkvarhdword 
50780Partial energy meter active energy pro- curement systemkWhdword 
50782Partial energy meter inductive reactive energy systemkvarhdword 
50784Partial energy meter apparent energy systemkVAhdword 
50786Partial energy meter active energy sup- ply systemkWhdword 
50788Partial energy meter capacitive reactive energy systemkvarhdword 