Connect Phoenix Contact to the computer through a USB-to-serial or RS485 adapter and read its registers in your browser: click "Read register values online" under the model (Chrome or Edge, nothing to install). The tables below list the MODBUS offset, unit, data type and scale of every register shown.
For logging 24/7 into a database, CSV files or Excel, use the Advanced Serial Data Logger (for MODBUS RTU) or Advanced TCP/IP Data Logger (for MODBUS TCP): they poll the complete map of every model on this page and provide continuous Phoenix Contact data logging and capture.
Do you not know the meter address? Scan the device address online
Phoenix Contact (EEM-EM3xx,EM325,EM355,EM375,EM327,EM357,EM377) - MODBUS Maps
Connection and addressing notes
- Function codes
- 03 read
- Register addressing
- decimal and hex (e.g. 4096 = 0x1000)
- Data format
- 32-bit float values occupy 2 registers
Registers in the map: 164 (the first 50 are listed below; the browser reader and the data loggers use the complete map). function 3 (holding registers). byte order big-endian. data types: single.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 4096 | Conductor voltage to N U1 | V | single | |
| 4098 | Conductor voltage to N U2 | V | single | |
| 4100 | Conductor voltage to N U3 | V | single | |
| 4102 | Conductor voltage to conductor U12 | V | single | |
| 4104 | Conductor voltage to conductor U23 | V | single | |
| 4106 | Conductor voltage to conductor U31 | V | single | |
| 4108 | External conductor voltage system | V | single | |
| 4110 | Current in conductor I1 | A | single | |
| 4112 | Current in conductor I2 | A | single | |
| 4114 | Current in conductor I3 | A | single | |
| 4116 | Current in conductor in | A | single | |
| 4118 | System current | A | single | |
| 4120 | Power factor phase 1 +/- | | single | |
| 4122 | Power factor phase 2 +/- | | single | |
| 4124 | Power factor phase 3 +/- | | single | |
| 4126 | System power factor | | single | |
| 4128 | Active power phase 1 +/- | W | single | |
| 4130 | Active power phase 2 +/- | W | single | |
| 4132 | Active power phase 3 +/- | W | single | |
| 4134 | Total active power +/- | W | single | |
| 4136 | Apparent power phase 1 | VA | single | |
| 4138 | Apparent power phase 2 | VA | single | |
| 4140 | Apparent power phase 3 | VA | single | |
| 4142 | Total apparent power +/- | VA | single | |
| 4144 | Reactive power phase 1 +/- | var | single | |
| 4146 | Reactive power phase 2 +/- | var | single | |
| 4148 | Reactive power phase 3 +/- | var | single | |
| 4150 | Total reactive power +/- | var | single | |
| 4152 | Frequency | Hz | single | |
| 4154 | Phase sequence 0.123 | | single | |
| 4352 | Total active energy procurement L1 | Wh | single | |
| 4354 | Total active energy procurement L2 | Wh | single | |
| 4356 | Total active energy procurement L3 | Wh | single | |
| 4358 | Total active energy procurement sum | Wh | single | |
| 4360 | Total active energy supply L1 | Wh | single | |
| 4362 | Total active energy supply L2 | Wh | single | |
| 4364 | Total active energy supply L3 | Wh | single | |
| 4366 | Total active energy supply sum | Wh | single | |
| 4368 | Total inductive apparent energy procurement L1 | VAh | single | |
| 4370 | Total inductive apparent energy procurement L2 | VAh | single | |
| 4372 | Total inductive apparent energy procurement L3 | VAh | single | |
| 4376 | Total inductive apparent energy supply L1 | VAh | single | |
| 4378 | Total inductive apparent energy supply L2 | VAh | single | |
| 4380 | Total inductive apparent energy supply L3 | VAh | single | |
| 4382 | Total inductive apparent energy supply sum | VAh | single | |
| 4384 | Total capacitive apparent energy procurement L1 | VAh | single | |
| 4386 | Total capacitive apparent energy procurement L2 | VAh | single | |
| 4388 | Total capacitive apparent energy procurement L3 | VAh | single | |
| 4390 | Total capacitive apparent energy procurement sum | VAh | single | |
| 4392 | Total capacitive apparent energy supply L1 | VAh | single | |
This is not the complete map: 50 of 164 registers are listed above. Click "Read register values online" to read any register of your device in the browser, or download the program to log the complete map.
Phoenix Contact (EEM-MA,EEM-MA3xx) - MODBUS Measurements
Connection and addressing notes
- Function codes
- 03 read
- Register addressing
- decimal and hex (e.g. 50512 = 0xC550)
- Data format
- 32-bit values occupy 2 registers
- Scaling
- UInt32 values are scaled by a factor (e.g. factor 100)
Registers in the map: 42. function 3 (holding registers). byte order big-endian. data types: dword, integer.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 10511 | Hour: operating hours counter | h | dword | ×0.01 |
| 10513 | U12: conductor voltage | V | dword | ×0.01 |
| 10515 | U23: conductor voltage | V | dword | ×0.01 |
| 10517 | U31: conductor voltage | V | dword | ×0.01 |
| 10519 | V1: conductor voltage to N | V | dword | ×0.01 |
| 10521 | V2: conductor voltage to N | V | dword | ×0.01 |
| 10523 | V3: conductor voltage to N | V | dword | ×0.01 |
| 10525 | F: frequency | Hz | dword | ×0.01 |
| 10527 | I1: current | A | dword | ×0.001 |
| 10529 | I2: current | A | dword | ×0.001 |
| 10531 | I3: current | A | dword | ×0.001 |
| 10533 | In: neutral conductor current | A | dword | ×0.001 |
| 10535 | P: total active power +/- | W | integer | ×10 |
| 10537 | Q: total reactive power +/- | var | integer | ×10 |
| 10539 | S: total apparent power | VA | dword | ×10 |
| 10541 | PF: total power factor -: capacitive and +: inductive | | integer | ×0.001 |
| 10543 | P1: active power phase 1 +/- | W | integer | ×10 |
| 10545 | P2: active power phase 2 +/- | W | integer | ×10 |
| 10547 | P3: active power phase 3 +/- | W | integer | ×10 |
| 10549 | Q1: reactive power phase 1 +/- | var | integer | ×10 |
| 10551 | Q2: reactive power phase 2 +/- | var | integer | ×10 |
| 10553 | Q3: reactive power phase 3 +/- | var | integer | ×10 |
| 10555 | S1: apparent power phase 1 | VA | dword | ×10 |
| 10557 | S2: apparent power phase 2 | VA | dword | ×10 |
| 10559 | S3: apparent power phase 3 | VA | dword | ×10 |
| 10561 | PF1; power factor, phase 1 -: capacitive and +: inductive | | integer | ×0.001 |
| 10563 | PF2; power factor, phase 2 -: capacitive and +: inductive | | integer | ×0.001 |
| 10565 | PF3; power factor, phase 3 -: capacitive and +: inductive | | integer | ×0.001 |
| 10567 | ISYS: mean current value | A | dword | ×0.001 |
| 10569 | USYS: mean value of line voltages | V | dword | ×0.01 |
| 10571 | VSYS: mean value of line voltages to N | V | dword | ×0.01 |
| 10767 | Hour: operating hours counter | h | dword | ×0.01 |
| 10769 | Total active energy procurement system | kWh | dword | |
| 10771 | Total inductive reactive energy system | kvarh | dword | |
| 10773 | Total apparent energy system | kVAh | dword | |
| 10775 | Total active energy supply system | kWh | dword | |
| 10777 | Total capacitive reactive energy system | kvarh | dword | |
| 10779 | Partial energy meter active energy pro- curement system | kWh | dword | |
| 10781 | Partial energy meter inductive reactive energy system | kvarh | dword | |
| 10783 | Partial energy meter apparent energy system | kVAh | dword | |
| 10785 | Partial energy meter active energy sup- ply system | kWh | dword | |
| 10787 | Partial energy meter capacitive reactive energy system | kvarh | dword | |
Phoenix Contact (EEM-MA3xx) - MODBUS Values
Connection and addressing notes
- Function codes
- 03 read
- Register addressing
- decimal and hex (e.g. 50512 = 0xC550)
- Data format
- 32-bit values occupy 2 registers
- Scaling
- UInt32 values are scaled by a factor (e.g. factor 100)
Registers in the map: 42. function 3 (holding registers). byte order big-endian. data types: dword, integer.
| MODBUS offset | Description | Units | Data type | Scale |
|---|
| 50512 | Hour: operating hours counter | h | dword | ×0.01 |
| 50514 | U12: conductor voltage | V | dword | ×0.01 |
| 50516 | U23: conductor voltage | V | dword | ×0.01 |
| 50518 | U31: conductor voltage | V | dword | ×0.01 |
| 50520 | V1: conductor voltage to N | V | dword | ×0.01 |
| 50522 | V2: conductor voltage to N | V | dword | ×0.01 |
| 50524 | V3: conductor voltage to N | V | dword | ×0.01 |
| 50526 | F: frequency | Hz | dword | ×0.01 |
| 50528 | I1: current | A | dword | ×0.001 |
| 50530 | I2: current | A | dword | ×0.001 |
| 50532 | I3: current | A | dword | ×0.001 |
| 50534 | In: neutral conductor current | A | dword | ×0.001 |
| 50536 | Sum P: total active power +/- | W | integer | ×10 |
| 50538 | Sum Q: total reactive power +/- | var | integer | ×10 |
| 50540 | Sum S: total apparent power | VA | dword | ×10 |
| 50542 | Sum PF: total power factor -: capacitive and +: inductive | | integer | ×0.001 |
| 50544 | P1: active power phase 1 +/- | W | integer | ×10 |
| 50546 | P2: active power phase 2 +/- | W | integer | ×10 |
| 50548 | P3: active power phase 3 +/- | W | integer | ×10 |
| 50550 | Q1: reactive power phase 1 +/- | var | integer | ×10 |
| 50552 | Q2: reactive power phase 2 +/- | var | integer | ×10 |
| 50554 | Q3: reactive power phase 3 +/- | var | integer | ×10 |
| 50556 | S1: apparent power phase 1 | VA | dword | ×10 |
| 50558 | S2: apparent power phase 2 | VA | dword | ×10 |
| 50560 | S3: apparent power phase 3 | VA | dword | ×10 |
| 50562 | PF1; power factor, phase 1 -: capacitive and +: inductive | | integer | ×0.001 |
| 50564 | PF2; power factor, phase 2 -: capacitive and +: inductive | | integer | ×0.001 |
| 50566 | PF3; power factor, phase 3 -: capacitive and +: inductive | | integer | ×0.001 |
| 50568 | ISYS: mean current value | A | dword | ×0.001 |
| 50570 | USYS: mean value of line voltages | V | dword | ×0.01 |
| 50572 | VSYS: mean value of line voltages to N | V | dword | ×0.01 |
| 50768 | Hour: operating hours counter | h | dword | ×0.01 |
| 50770 | Total active energy procurement system | kWh | dword | |
| 50772 | Total inductive reactive energy system | kvarh | dword | |
| 50774 | Total apparent energy system | kVAh | dword | |
| 50776 | Total active energy supply system | kWh | dword | |
| 50778 | Total capacitive reactive energy system | kvarh | dword | |
| 50780 | Partial energy meter active energy pro- curement system | kWh | dword | |
| 50782 | Partial energy meter inductive reactive energy system | kvarh | dword | |
| 50784 | Partial energy meter apparent energy system | kVAh | dword | |
| 50786 | Partial energy meter active energy sup- ply system | kWh | dword | |
| 50788 | Partial energy meter capacitive reactive energy system | kvarh | dword | |