Carlo Gavazzi (WM3-96) data logger. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
4A L1Adword
8W L1 dword
12V L2-NVdword
16A L2Adword
20W L2 dword
24V L3-NVdword
28A L3Adword
32W L3 dword
36V L1Vdword
40V L2Vdword
44V L3Vdword
48VA L1 dword
52Var L1 dword
56PF L1 dword
60VA L2 dword
64Var L2 dword
68PF L2 dword
72VA L3 dword
76Var L3 dword
80PF L3 dword
84VVdword
88A NAdword
92W dword
96VA dword
100Var dword
104PF dword
108THD V1 dword
112THDe V1 dword
116THDo V1 dword
120THD V2 dword
124THDe V2 dword
128THDo V2 dword
132THD V3 dword
136THDe V3 dword
140THDo V3 dword
144THD A1 dword
148THDe A1 dword
152THDo A1 dword
156THD A2 dword
160THDe A2 dword
164THDo A2 dword
168THD A3 dword
172THDe A3 dword
176THDo A3 dword
180A dmdAdword
184VA dmd dword
188TPF avg dword
192W dmd dword
196HzHzdword
200ASY dword
204VL-N dword
208UN dword
232Unit V, A/P dword
236KWh+, TOTALE, period PERIODKWhdword
240KWh-, TOTALE, period PERIODKWhdword
244KVARh+, TOTALE, period PERIODKVARhdword
248KVARh-, TOTALE, period PERIODKVARhdword
252KWh+, TOTALE, period PERIODKWhdword
253KWh-, TOTALE, period PERIODKWhdword
254KVARh+, TOTALE, period PERIODKVARhdword
255KVARh-, TOTALE, period PERIODKVARhdword
256KWh+, WINTER, period 1KWhdword
260KWh-, WINTER, period 1KWhdword
264KVARh+, WINTER, period 1KVARhdword
268KVARh-, WINTER, period 1KVARhdword
272KWh+, WINTER, period 2KWhdword
276KWh-, WINTER, period 2KWhdword
280KVARh+, WINTER, period 2KVARhdword
284KVARh-, WINTER, period 2KVARhdword
288KWh+, WINTER, period 3KWhdword
292KWh-, WINTER, period 3KWhdword
296KVARh+, WINTER, period 3KVARhdword
300KVARh-, WINTER, period 3KVARhdword
304KWh+, WINTER, period 4KWhdword
308KWh-, WINTER, period 4KWhdword
312KVARh+, WINTER, period 4KVARhdword
316KVARh-, WINTER, period 4KVARhdword
320KWh+, SUMMER, period 1KWhdword
324KWh-, SUMMER, period 1KWhdword
328KVARh+, SUMMER, period 1KVARhdword
332KVARh-, SUMMER, period 1KVARhdword
336KWh+, SUMMER, period 2KWhdword
340KWh-, SUMMER, period 2KWhdword
344KVARh+, SUMMER, period 2KVARhdword
348KVARh-, SUMMER, period 2KVARhdword
352KWh+, SUMMER, period 3KWhdword
356KWh-, SUMMER, period 3KWhdword
360KVARh+, SUMMER, period 3KVARhdword
364KVARh-, SUMMER, period 3KVARhdword
368KWh+, SUMMER, period 4KWhdword
372KWh-, SUMMER, period 4KWhdword
376KVARh+, SUMMER, period 4KVARhdword
380KVARh-, SUMMER, period 4KVARhdword
384KWh+, HOLYDAY, period 1KWhdword
388KWh-, HOLYDAY, period 1KWhdword
392KVARh+, HOLYDAY, period 1KVARhdword
396KVARh-, HOLYDAY, period 1KVARhdword
400KWh+, HOLYDAY, period 2KWhdword
404KWh-, HOLYDAY, period 2KWhdword
408KVARh+, HOLYDAY, period 2KVARhdword
There are more MODBUS items for this device. Please, download the program.

Carlo Gavazzi (EM100,ET100) data logging
Carlo Gavazzi (EM24) data logging
Carlo Gavazzi (EM26) data logging
Carlo Gavazzi (EM270) data logging
Carlo Gavazzi (EM271) data logging
Carlo Gavazzi (EM300,ET300) data logging
Carlo Gavazzi (EM33) data logging
Carlo Gavazzi (WM14, CPT A) data logging
Carlo Gavazzi (WM30, WM40) data logging
Carlo Gavazzi (WM3-96) data logging
Carlo Gavazzi EM21 data logging

Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.