Jiangsu Sfere Electric (D1900) data logger. MODBUS registers map.
This data is being extracted with help of the "Advanced Serial Data Logger" or "Advanced TCP/IP Data Logger" software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
262 | Import active energy | Wh | integer |
264 | Export active enregy | Wh | integer |
266 | Import reactive energy | varh | integer |
268 | Export reactive energy | varh | integer |
270 | Apparent energy | V | integer |
272 | First quadrant reactive energy | varh | integer |
274 | Second quadrant reactive energy | varh | integer |
276 | Third quadrant reactive energy | varh | integer |
278 | Fourth quadrant reactive energy | varh | integer |
280 | Active energy [total | Wh | integer |
282 | Active energy [tip | Wh | integer |
284 | Active energy [peak | Wh | integer |
286 | Active energy [level | Wh | integer |
288 | Active energy [valley | Wh | integer |
290 | Active energy of this month [total/tip/peak/level/valley | Wh | integer |
300 | Active energy of last month [total/tip/peak/level/valley | Wh | integer |
310 | Active energy of the month before | Wh | integer |
2 | Current | A | single |
4 | Active power | kW | single |
6 | Reactive power | kvar | single |
8 | Apparent power | kVA | single |
10 | Power factor | | single |
12 | Frequency | Hz | single |
14 | Import active energy | kW | single |
16 | Export active energy | kW | single |
18 | Import reactive energy | kvar | single |
1550 | Max. reactive power demand value of this month | var | integer |
1551 | Max. apparent power demand value of this month | V | integer |
1552 | Active power demand value at present | W | integer |
1553 | Reactive power demand value at present | var | integer |
1554 | Apparent power demand value at present | V | integer |
1556 | Power on record times and year | a | string |
1557 | Power on record month and data | a | string |
1558 | Power on record hour and minute | | string |
1559 | Programming record times and year | a | string |
1560 | Programming record month and day | a | string |
1561 | Programming record hour and minute | | string |
1562 | Energy clearing times and year | a | string |
1563 | Energy clearing month and day | a | string |
1564 | Energy clearing hour and minute | | string |
512 | Voltage | V | integer |
513 | Current | A | integer |
514 | Active power | W | integer |
515 | Reactive power | var | integer |
516 | Apparent power | V | integer |
517 | Power factor | | integer |
518 | Frequency | Hz | integer |
1536 | Max. voltage value | V | integer |
1537 | Max. current value | A | integer |
1538 | Max. active power value | W | integer |
1539 | Max. reactive power value | var | integer |
1540 | Max. apparent power value | V | integer |
1541 | Max. active power demand value | W | integer |
1542 | Max. reactive power demand value | var | integer |
1543 | Max. apparent power demand value | V | integer |
1544 | Max. voltage value of this month | V | integer |
1545 | Max. current value of this month | A | integer |
1546 | Max. active power value of this month | W | integer |
1547 | Max. reactive power value of this month | var | integer |
1548 | Max. apparent power value of this month | V | integer |
1549 | Max. active power demand value | W | integer |
Jiangsu Sfere Electric (D1900) data logging
Jiangsu Sfere Electric (D1900, 3 phases) data logging