Northern Design MultiCube Modbus logging. MODBUS registers map.


This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.

MODBUS offsetDescriptionUnitsData type
512eScale dword
514kWhkWhdword
516kVAhkVAhdword
518Kvarh inductivekvarhdword
520Kvarh capacitivekvarhdword
522Import kvarhkvarhdword
524Export kWhkWhdword
526Export kvarhkvarhdword
2816System kWkWword
2817System kVAkVAword
2818System kvarkvarword
2819System PF word
2820Frequency word
2821Phase 1 voltsVoltsword
2822Phase 1 ampsAmpsword
2823Phase 1 kWkWword
2824Phase 2 voltsVoltsword
2825Phase 2 ampsAmpsword
2826Phase 2 kWkWword
2827Phase 3 voltsVoltsword
2828Phase 3 ampsAmpsword
2829Phase 3 kWkWword
2830Phase 1 PF word
2831Phase 2 PF word
2832Phase 3 PF word
2833Ph1-Ph2 voltsVoltsword
2834Ph2-Ph3 voltsVoltsword
2835Ph3-Ph1 voltsVoltsword
2836Neutral current word
2837Amps scale kiAmpsword
2838Phase volts scale kvpVoltsword
2839Line volts scale kvlVoltsword
2840Power scale kp word
3072Phase 1 kVAkVAword
3073Phase 2 kVAkVAword
3074Phase 3 kVAkVAword
3075Phase 1 kvarkvarword
3076Phase 2 kvarkvarword
3077Phase 3 kvarkvarword
3328Peak hold ph1 ampsAmpsword
3329Peak hold ph2 ampsAmpsword
3330Peak hold ph3 ampsAmpsword
3331Peak hold ph1 voltsVoltsword
3332Peak hold ph2 voltsVoltsword
3333Peak hold ph3 voltsVoltsword
3334Peak hold kW demandkWword
3335KW demand periodKWword
3336KW demandKWword
3584CT primaryAmpsword
3585Nominal voltsVoltsword
There are more MODBUS items for this device. Please, download the program.