Northern Design MultiCube Modbus data logging. MODBUS registers map.
This data is being extracted with help of the "Advanced Serial Data Logger" or "Advanced TCP/IP Data Logger" software only. It may not applicable for other software titles.
MODBUS offset | Description | Units | Data type |
512 | eScale | | dword |
514 | kWh | kWh | dword |
516 | kVAh | kVAh | dword |
518 | Kvarh inductive | kvarh | dword |
520 | Kvarh capacitive | kvarh | dword |
522 | Import kvarh | kvarh | dword |
524 | Export kWh | kWh | dword |
526 | Export kvarh | kvarh | dword |
2816 | System kW | kW | word |
2817 | System kVA | kVA | word |
2818 | System kvar | kvar | word |
2819 | System PF | | word |
2820 | Frequency | | word |
2821 | Phase 1 volts | Volts | word |
2822 | Phase 1 amps | Amps | word |
2823 | Phase 1 kW | kW | word |
2824 | Phase 2 volts | Volts | word |
2825 | Phase 2 amps | Amps | word |
2826 | Phase 2 kW | kW | word |
2827 | Phase 3 volts | Volts | word |
2828 | Phase 3 amps | Amps | word |
2829 | Phase 3 kW | kW | word |
2830 | Phase 1 PF | | word |
2831 | Phase 2 PF | | word |
2832 | Phase 3 PF | | word |
2833 | Ph1-Ph2 volts | Volts | word |
2834 | Ph2-Ph3 volts | Volts | word |
2835 | Ph3-Ph1 volts | Volts | word |
2836 | Neutral current | | word |
2837 | Amps scale ki | Amps | word |
2838 | Phase volts scale kvp | Volts | word |
2839 | Line volts scale kvl | Volts | word |
2840 | Power scale kp | | word |
3072 | Phase 1 kVA | kVA | word |
3073 | Phase 2 kVA | kVA | word |
3074 | Phase 3 kVA | kVA | word |
3075 | Phase 1 kvar | kvar | word |
3076 | Phase 2 kvar | kvar | word |
3077 | Phase 3 kvar | kvar | word |
3328 | Peak hold ph1 amps | Amps | word |
3329 | Peak hold ph2 amps | Amps | word |
3330 | Peak hold ph3 amps | Amps | word |
3331 | Peak hold ph1 volts | Volts | word |
3332 | Peak hold ph2 volts | Volts | word |
3333 | Peak hold ph3 volts | Volts | word |
3334 | Peak hold kW demand | kW | word |
3335 | KW demand period | KW | word |
3336 | KW demand | KW | word |
3584 | CT primary | Amps | word |
3585 | Nominal volts | Volts | word |
3586 | Pulse 1 rate | | word |
3587 | Pulse 2 rate (= pulse 1 rate) | | word |
3588 | Baud | | word |
3589 | Modbus ID | | word |
3590 | Meter model | | word |
3591 | Meter type | | word |
3592 | Firmware version | | word |
3593 | Current demand period | | word |
3594 | Pulse ON time | | word |
3595 | Security code | | word |
3840 | Peak ph1 amps demand | Amps | word |
3841 | Peak ph2 amps demand | Amps | word |
3842 | Peak ph3 amps demand | Amps | word |
3843 | Peak ph1 volts demand | Volts | word |
3844 | Peak ph2 volts demand | Volts | word |
3845 | Peak ph3 volts demand | Volts | word |
4096 | Ph1 amps demand | Amps | word |
4097 | Ph2 amps demand | Amps | word |
4098 | Ph3 amps demand | Amps | word |
4099 | Ph1 volts demand | Volts | word |
4100 | Ph2 volts demand | Volts | word |
4101 | Ph3 volts demand | Volts | word |
4352 | V1 % THD | | word |
4353 | V2 % THD | | word |
4354 | V3 % THD | | word |
4355 | I1 % THD | | word |
4356 | I2 % THD | | word |
4357 | I3 % THD | | word |
4608 | kW demand | kW | word |
4609 | kVA demand | kVA | word |
4610 | Kvar demand | Kvar | word |
4611 | Peak hold kW demand | kW | word |
4612 | Peak hold kVA demand | kVA | word |
4613 | Peak hold kvar demand | kvar | word |
Northern Design Cube 300 Modbus data logging
Northern Design Cube 350 Cube 400 Rail 350 Modbus data logging
Northern Design MultiCube Modbus data logging
Northern Design PM390 data logging