Ohio Semitronics (WVx,WTx,WMx) logging - MODBUS registers map
This data is being extracted with the help of the Advanced Serial Data Logger (MODBUS RTU,ASCII) or Advanced TCP/IP Data Logger (MODBUS TCP) software only. It may not applicable for other software titles.
MODBUS offset
Description
Units
Data type
5000
Meter name
16 char
string
5008
Meter serial number
16 char
string
5016
Meter firmware version
8 char
string
5020
Serial firmware version
8 char
string
5206
Power factor
-1 to 1
single
5232
Frequency
0 to 1,000
single
5246
Power factor (l1)
single
5248
Power factor (l2)
single
5250
Power factor (l3)
single
5300
Watt hr consumed pulse counter
0-2^31
dword
5302
Watt hr generated pulse counter
0-2^31
dword
5304
Var hr pulse counter
0-2^31
dword
Note: Products and companies mentioned here are used only for definition and identification purposes and can be trademarks and/or registered trademarks of the respective companies.